cc/td/doc/product/ong/15216/216edf
hometocprevnextglossaryfeedbacksearchhelp
PDF

Table Of Contents

Troubleshooting

10.1  Alarm Indicators

10.1.1  LEDs and Office Alarms

10.1.2  Troubleshooting Optical Alarms

10.1.3  Troubleshooting Equipment Alarms

10.2  Typical Troubleshooting Scenarios

10.2.1  No Output Power after Adjusting Gain Settings

10.2.2  2.0.1 to 2.2.1 Upgrade Attempt

10.2.3  Image File Download Incomplete

10.2.4  Primary Boot Up Failure

10.2.5  Complete Boot Up Failure

10.2.6  No Response from RS-232 Port

10.2.7  No Response from LAN Port

10.2.8  LAN Port Activity LED Stays On

10.2.9  Lost Password

10.3  Status Information Needed by Cisco TAC


Troubleshooting


This chapter presents basic fault information and diagnosis (troubleshooting) procedures for the 2.1.0, 2.2.1, 2.3.0, and 2.4.0 product releases of the Cisco ONS 15216 EDFA2. Only TL1 information about the alarm notifications and commands is provided.

This chapter describes the behavior of the ONS 15216 EDFA2 in the most expected troubleshooting situations. It does not address all possible causes of a particular situation or all possible solutions. For additional help, please review the Release Notes for the software version(s) being used.

If a situation is experienced that cannot be resolved, contact the Cisco Technical Assistance Center (TAC) for help (see the "Obtaining Technical Assistance" section). For all interactions with the Cisco TAC, have the current ONS 15216 EDFA2 status prepared as described in the "Status Information Needed by Cisco TAC" section.

This chapter includes the following sections:

Alarm Indicators

LEDs and Office Alarms

Troubleshooting Optical Alarms

Troubleshooting Equipment Alarms

Typical Troubleshooting Scenarios

No Output Power after Adjusting Gain Settings

2.0.1 to 2.2.1 Upgrade Attempt

Image File Download Incomplete

Primary Boot Up Failure

Complete Boot Up Failure

No Response from RS-232 Port

No Response from LAN Port

LAN Port Activity LED Stays On

Lost Password

Status Information Needed by Cisco TAC

10.1  Alarm Indicators

This section provides alarm indications, including LEDs and alarms.

10.1.1  LEDs and Office Alarms

The front panel of the ONS 15216 EDFA2 has five LEDs:

POWER

FAIL

LOS

Ethernet socket (2)

On the left side of the front panel of the ONS 15216 EDFA2 are the POWER, FAIL, and LOS alarm LEDs. The Ethernet LEDs are located at the top left and right sides of the Ethernet LAN port. When the module is powered on, a LED test is performed. For information about the LED test sequence, see the "Rack Installation and Power Supply Connection Procedures" section.

The POWER, FAIL, and LOS LEDs correspond to Office Alarm conditions sent via the RJ-45 ALARM port (if used). For additional alarm contact pinout information, see the "Alarm Out Relay Interface (RJ-45)" section.

10.1.1.1  POWER LED (Green)

The POWER LED is green when on. This LED functions as follows:

On: -48 VDC power supply is within allowable range. (Power Bus A and B are powered normally.)

Off: If in duplex mode, both Power Bus A and B have failed (below -40 VDC) and remain below the minimum turn-on supply voltage (-43 VDC). If in simplex mode, Power Bus A has failed (below -40 VDC) and remains below the minimum turn-on supply voltage (-43 VDC). Note that the power bus turn-off threshold has a 1.5V tolerance.

Flashing: PWRBUSA or PWRBUSB alarm. If in duplex mode, Power Bus A, or B, or both are out of the user-settable tolerance range. If in simplex mode, Power Bus A is out of the user-settable tolerance range. The tolerance range is defined by PWRBUSMIN and PWRBUSMAX. The power bus alarm threshold has a 1.5V tolerance and a 1.0V hysteresis.

See PWRBUSA and PWRBUSB (Power Bus) Alarms for information about how to troubleshoot a Power Bus alarm.

Office Alarm: In the off condition, the first pair (0) of alarm relay contacts in the RJ-45 ALARM connector changes from a normally open condition to a closed condition. The LED and alarm relay automatically reset when the alarm condition clears.

In the flashing condition, the fourth pair (3) of alarm relay contacts in the RJ-45 ALARM connector changes from a normally open condition to a closed condition. The LED and alarm relay automatically reset when the alarm condition clears.

10.1.1.2  FAIL LED (Red)

The FAIL LED is red when on. This LED indicates all alarm conditions except POWER and LOS, which have their own LEDs. The FAIL LED functions as follows:

Off: The gain, output power, case temperature, laser pump current, and laser pump temperature are all within their specified ranges (or -48 VDC power has failed).

On: GAIN, LPOUT, CTMP, LCRNT1, LCRNT2, LTMP1, and/or LTMP2 alarm. The gain, output power, case temperature, laser pump current, and/or laser pump temperature are out of tolerance. (A major internal failure has occurred.)

If on, access the ONS 15216 EDFA2 to determine which alarms have occurred ( Example 10-1). See the sections Troubleshooting Optical Alarms and Troubleshooting Equipment Alarms that follow for information about how to troubleshoot a particular alarm.

Office Alarm: In the on condition, the second pair (1) of alarm relay contacts in the RJ-45 ALARM connector changes from a normally open to a closed condition. The LED and alarm relay automatically reset when the alarm condition clears.

Example 10-1 Checking Alarm Source

Amp01:ONS15216 EDFA2> RTRV-ALM-ALL:AMP01::123::,,,,,;

þAmp01 2004-03-17 00:29:54
M þ123 COMPLD
þ"EQPT,EQPT:MN,CTMP,NSA,3-17,0-29-43,,:\"Case Temperature Out Of Range\""
;

10.1.1.3  LOS LED (Yellow)

The Loss of Signal (LOS) LED is yellow when on. This LED functions as follows:

Off: The optical input power is above the user-settable minimum threshold (or -48 VDC power has failed).

On: LOS alarm. The optical input power to the ONS 15216 EDFA2 is below the threshold defined by LOSTH. The value of LOSHYST provides the hysteresis required for the alarm to clear.

If on, see LOS (Loss of Signal) Alarm for information about how to troubleshoot the LOS alarm.

Office Alarm: In the on condition, the third pair (2) of alarm relay contacts in the RJ-45 ALARM connector changes from a normally open condition to a closed condition. The LED and alarm relay automatically reset when the alarm condition clears.

10.1.1.4  Ethernet Socket LEDs

Two LEDs are located at the top left and right sides of the Ethernet socket (LAN port). These LEDs are both green. These LEDs function as follows:

If the left Ethernet socket LED is on, the link is up.

If the right Ethernet socket LED is on or flashing, there is Ethernet activity (traffic).


Note If the system is powered up without an Ethernet cable in the Ethernet socket (LAN port), the activity LED (right side) turns on and remains on even if there is not Ethernet traffic. See "LAN Port Activity LED Stays On" section.


10.1.2  Troubleshooting Optical Alarms

The ONS 15216 EDFA2 amplifier has two main categories of alarms: optical (DWDM) and equipment (EQPT). The optical alarms are directly related to the signal amplification and are usually service affecting. The ONS 15216 EDFA2 has three Optical alarms:

LOS

GAIN

LPOUT


Warning Follow all directions and warning labels when working with optical fibers. To prevent eye damage, never look directly into a fiber or connector.


Most optical failures are due to dirty or damaged connectors, so it is very important to clean all connectors. Note that there is a connector inside the transmission equipment and that a problem may come from there as well as from the patchcord.

To clean the optical connectors, follow the procedure below:


Step 1 Turn off the optical amplifier and disconnect all optical power.


Warning Adhere to all safety procedures. Optical power can cause physical injury or damage to equipment. Turn off the device and disconnect all optical power before cleaning or inspection.


Step 2 Remove and inspect the patchcord connectors using an optical fiber scope. Clean if required using a proprietary cartridge cleaner.

Step 3 Re-inspect the connector to verify cleanliness and clean again if necessary.

Step 4 If a removed patchcord connector is dirty, use a 2.5_m lint-free swab and insert it into the corresponding connector adapter sleeve. Gently rotate the swab on the opposing connector's end-face.

Step 5 Replace the dust cover on the adapters or reattach cables.


10.1.2.1  LOS (Loss of Signal) Alarm

This alarm is generated when the input signal is below the value of LOSTH. The value of LOSHYST provides the hysteresis required for the alarm to clear. Possible causes for this alarm are:

Input power is below threshold value: Verify that the threshold value is set to the correct value for the particular ONS 15216 EDFA2 application (RTRV-TH-DWDM). Read the input power using the RTRV-DWDM command.

No optical signal is present at the input (RTRV-DWDM): Verify that the transmitter is working correctly and that the upstream fiber is not broken (RTRV-DWDM).

Power meter value is higher than the reading of the ONS 15216 EDFA2 software: Clean connector of fiber patchcord as well as the one from inside the ONS 15216 EDFA2 by removing the fiber access panel.


Warning Follow all directions and warning labels when working with optical fibers. To prevent eye damage, never look directly into a fiber or connector.


10.1.2.2  GAIN (Gain Out of Range) Alarm

This alarm is only valid when the ONS 15216 EDFA2 is in GAINTEMP mode. It occurs when the value of OVERALLGAINMEASURED has deviated more than 1.25 dB from the manufacturer-defined set point's allowable range. This condition has a 0.25 dB hysteresis.

The GAIN alarm is also triggered if the value of INPWRDBM goes outside the manufacturer-defined range by more than 0.7 dB. This condition has a 0.2 dB hysteresis.

Use the RTRV-DWDM command to retrieve the values of OVERALLGAINMEASURED and INPWRDBM.

If both GAIN and LOS alarm conditions occur at the same time, only the LOS alarm is generated via TL1. The GAIN alarm has a soak period of 1-2 seconds before being raised or cleared.

Possible causes for this alarm are:

Input power is out of range: Verify that for the current gain setting, the input power is within the range. For example, if the Gain = 22, then the input range is -27 to -5 dBm. Every dB taken from the Gain is added to the input range, so if the Gain =21, then the input range is -26 to -4 dBm.

VOA attenuation is drifting out of range: Verify that the VOA set value approximately equals the VOA current value.

To determine this, you must use the ASH shell. You can begin an ASH Telnet session using the IP address of the ONS 15216 EDFA2 followed by port 8023.

telnet ONS_15216_EDFA2_IP_Address 8023

The following formula provides the setting of the VOA attenuation (in constGainTempComp mode):

"VOA set value (in units of 10 dB)" =
"snmp attribute get local cerent15216EdfaPumpStatusGain 1" -
"snmp attribute get local cerent15216EdfaConstGainOverallGain"

The value of cerent15216EdfaPumpStatusGain 1 is the fixed gain of the amplifier module. The value of cerent15216EdfaConstGainOverallGain is the set target gain. Note that the minimum VOA value is approximately 1 dB, which corresponds to the maximum Gain of approximately 22 dB.

The following formula provides the current value of the VOA attenuation:

"VOA current value (in units of 100 dB)" =
"snmp attribute get local cerent15216EdfaInPowerdBm" -
"snmp attribute get local cerent15216EdfaPumpStatusInPowerdBm 1"

The value of cerent15216EdfaInPowerdBm (INPWRDBM) is the current signal power at the input before the VOA. The value of cerent15216EdfaPumpStatusInPowerdBm 1 is the signal power after the VOA.

If the "VOA set value" is different than "VOA current value" by more than a typical variation of up to 0.5 dB, the unit must be returned to Cisco for repair.

10.1.2.3  LPOUT (Loss of Output Power) Alarm

This alarm is valid only when the ONS 15216 EDFA2 is in OPWR mode, which is rare because this mode applies to few applications and is generally not recommended. This alarm occurs if the unit is in OPWR mode and the output power is deviating more than the value of LPOUTDEV from the value of LPOUTSETPT. The value of LPOUTHYST is used to clear the alarm. Use RTRV-TH-DWDM to find the threshold values.

If both LPOUT and GAIN or LOS alarm conditions occur at the same time, only the GAIN or LOS alarm is generated via TL1.

Possible causes for this alarm are:

The input power may be too low to achieve the output power setting: Reduce the value of PUMP2CTRLVALUE using the ED-DWDM command until the alarm clears.

The LPOUTDEV value may be set too low for practical use: Increase the value of LPOUTDEV using the RTRV-TH-DWDM command.

10.1.3  Troubleshooting Equipment Alarms

The ONS 15216 EDFA2 amplifier has two main categories of alarms: optical (DWDM) and equipment (EQPT). The equipment alarms are directly related to general equipment conditions in the unit. The ONS 15216 EDFA2 has seven equipment alarms:

CTMP

LCRNT1

LCRNT2

LTMP1

LTMP2

PWRBUSA

PWRBUSB

10.1.3.1  CTMP (Case Temperature Out of Range) Alarm

This alarm occurs when the case temperature is out of the threshold range as defined by MINCTMP and MAXCTMP. The values of MINCTMPHYST and MAXCTMPHYST provide the hysteresis required for the alarm to clear. Possible causes for this alarm are:

The Min and Max thresholds may not reflect the ambient temperature where the ONS 15216 EDFA2 is located: Use RTRV-TH-EQPT to get the Min and Max temperature threshold and change the threshold using SET-TH-EQPT.

The ambient temperature is too high for a legitimate case temperature alarm to clear: Shut down the ONS 15216 EDFA2 and allow time for it to cool, and do not repower it until the ambient temperature is reduced.

10.1.3.2  LCRNT1 and LCRNT2 (Excessive Pump Current) Alarms

These alarms occur when the input power exceeds input range and the ONS 15216 EDFA2 is overdriving the pump laser to try to get the target Gain value. The manufacturer defines this condition as the drive current at greater than 95% of end of life value. The current must drop to 90% of the end-of-life value for the alarm to clear. Possible causes for this alarm are:

The input power is too high for the gain setting: Reduce the input power by using an external attenuator or by changing the OVERALLGAIN value using the ED-DWDM command.

One pump laser is degrading: The unit needs to be replaced. Contact the Cisco TAC.

10.1.3.3  LTMP1 and LTMP2 (Excessive Pump Temperature) Alarms

These alarms occur when the pump laser has reached a critical temperature threshold. That is, the chip temperature is deviating more than 10 degrees C from the manufacturer-defined set point.

Ambient temperature is too high so the laser can't cool down: This condition is usually associated with a CTMP alarm. See the CTMP (Case Temperature Out of Range) Alarm section above.

The ONS 15216 EDFA2 has been operating with excessive pump current for a long period of time, causing the pump(s) to overheat: This condition is usually associated with a LCRNT1 or LCRNT2 alarm. See the LCRNT1 and LCRNT2 (Excessive Pump Current) Alarms section above.

10.1.3.4  PWRBUSA and PWRBUSB (Power Bus) Alarms

These alarms occur when the Power Bus voltage is out of the threshold range as defined by PWRBUSMIN and PWRBUSMAX. The power bus threshold has a 1.5V tolerance and a 1.0V hysteresis. The 1.5V tolerance prevents early alarm conditions due to a potential ±1.5V inaccuracy in the ONS 15216 EDFA2 voltage measurement.

The problem may be an inappropriate setting of the Power Bus alarm or a power failure. First, check the alarm thresholds using RTRV-TH-EQPT ( Example 10-2). The default values are POWERBUSMIN=420 (-42 VDC) and POWERBUSMAX=570 (-57 VDC). The command RTRV-ALM-EQPT responds with which POWERBUS is outside of the range. If Power Bus B is not being used, check that PWRBUSMODE=SIMPLEX using RTRV-TH-EQPT. If needed, use the command ED-EQPT to set the POWERBUSMODE to SIMPLEX ( Example 10-3). If all the settings are correct, verify the DC voltage of the power source.

Example 10-2 Checking Power Thresholds

Amp01:ONS15216 EDFA2> RTRV-TH-EQPT:Amp01:PWR-A:123:PWRBUSMIN;

þAmp01 2004-03-17 00:02:15
M þ123 COMPLD
þ"PWR-A:PWRBUSMIN,,,420"
þ"PWR-A:PWRBUSMAX,,,570"
;

Example 10-3 Changing Power Bus Mode to Simplex

Amp01:ONS15216 EDFA2> RTRV-ALM-EQPT:Amp01:PWR-B:124;

þAmp01 2004-03-17 00:03:48
M þ124 COMPLD
þ"PWR-B:MN,PWRBUSB,NSA,3-16,20-39-21,,:\"Power Bus B Alarm\""
;
Amp01:ONS15216 EDFA2> ED-EQPT:SID:PWR-B:125:Amp01::PWRBUSMODE=SIMPLEX;

þAmp01 2004-03-17 00:23:07
A þ1 REPT EVT EQPT
þ"PWR-B:PWRBUSMODE,TC,3-17,0-23-7,,,,:\"Power Bus Mode Changed\""
;

þAmp01 2004-03-17 00:23:08
A þ2 REPT ALM EQPT
þ"PWR-B:CL,PWRBUSB,NSA,3-17,0-23-8,,:\"Power Bus B Alarm\""
;

þAmp01 2004-03-17 00:23:08
M þ125 COMPLD
þ/* ED-EQPT */
;

10.2  Typical Troubleshooting Scenarios

This section provides several troubleshooting scenarios.

10.2.1  No Output Power after Adjusting Gain Settings

The no output power after adjusting gain setting issue occurs only with software version 2.1.0.

Release Notes 2.1.0 Caveat CSCdy50894

Explanation    The VOA pre-attenuator is stuck at maximum attenuation if the gain setting is modified when the input power is below the minimum signal level.

Recommended Action    Use the following series of sample commands to recover from the VOA being stuck at high attenuation:

For TL1:

name:ONS15216 EDFA2> ED-DWDM:name:all:100:::PUMP1CTRLMODE=PWR,PUMP1CTRLVALUE=50;
name:ONS15216 EDFA2> ED-DWDM:name:all:101:::PREATT=10;
name:ONS15216 EDFA2> ED-DWDM:name:all:102:::PUMP1CTRLMODE=GAINTEMP;
name:ONS15216 EDFA2> ED-DWDM:name:all:103:::OVERALLGAIN=160;

For ASH:

ash:hostname:ONS15216 EDFA2> snmp attribute set local cerent15216EdfaPumpCfgConstPumpPower 1 50
ash:hostname:ONS15216 EDFA2> snmp attribute set local cerent15216EdfaPumpCfgControlMode 1 constPower
ash:hostname:ONS15216 EDFA2> snmp attribute set local cerent15216EdfaVariableGainPreAttenuation 10
ash:hostname:ONS15216 EDFA2> snmp attribute set local cerent15216EdfaConstGainOverallGain 160

10.2.2  2.0.1 to 2.2.1 Upgrade Attempt

To achieve a smooth software upgrade, the ONS 15216 EDFA2 must first get upgraded from software version v2.0.1 to v2.1.0 before being upgraded from v2.1.0 to v2.2.1.

If a unit has been upgraded directly from v2.0.1 to v2.2.1, some features of v2.2.1 may not operate properly. In addition, the CISCO15 user has only read write access and cannot perform administrative commands.

To fix this, the software must be reverted back to v2.0.1 using the uninstall procedure described in the 2.2.1 Release Notes, and then all firmware and software upgrade procedures must be performed in series, from v2.0.1 to v2.1.0 and then from v2.1.0 to v2.2.1. See the 2.1.0 and 2.2.1 Release Notes for the upgrade procedures.

10.2.3  Image File Download Incomplete

If there is insufficient space in the flash file system (FFS) during an image file download, the ONS 15216 EDFA2 may report that the download has completed successfully even though the file is incomplete. Follow the upgrade instructions precisely to ensure that the file downloads completely and the file length is checked.

If a new image does not boot correctly, check its file size using the ASH ffs file list command. The 2.0.1 image should be 1,683,299 bytes, the 2.1.0 image should be 2,021,467 bytes, and the 2.2.1 image should be 1,963,195 bytes. See the 2.3.0 Release Notes for the 2.3.0 image file size.

If the file length is incorrect, delete the file, clear FFS space, and download the image file again. See the 2.1.0, 2.2.1, and 2.3.0 Release Notes for the procedures.

10.2.4  Primary Boot Up Failure

If the primary software image fails to boot correctly, the ONS 15216 EDFA2 switches to booting from the second image. When this occurs, the RS-232 command line interface shows the switch from Image 0 to Image 1 as shown in Example 10-4.

Example 10-4 Bootup Switch to Second Image

*** EDFA Fw Boot Console (v2.3.15) ***

auto-boot
Loading Image (0)
open failed -1 file 15216EdfaSw_2.4.0
Loading Image (1)
.......................................................................................... .....................................................
Amplifier FW v4.27, available FW v4.27 - no FW upgrade.

If the bootup screen is not observed from the RS-232 port, the primary boot failure may be discovered by checking the RTRV-INV and RTRV-NE-GEN commands and seeing that the second boot file name is active instead of the first. See Example 10-5.

Example 10-5 Checking Boot File

Amp01:ONS15216 EDFA2> RTRV-INV:Amp01:ALL:123;
   Amp01 2002-01-12 08:01:05
M 123 COMPLD
   "EQPT:CLEI=IPI01AA0AAA,DESCR=ONS15216 EDFA2,NAME=Amp01,HARDWAREREV=74-2256-05-A0-B4,FIR MWAREREV=v2.3.15,SOFTWAREREV=v2.3.0,SERIALNUM=DIT0533000P,MFGNAME=Cisco Systems,MODELNAME= ONS216EDFA"
;
Amp01:ONS15216 EDFA2> RTRV-NE-GEN:Amp01::124;
   Amp01 2002-01-12 08:01:25
M 124 COMPLD
   "EQPT:NAME=Amp01,IPADDR=172.22.87.100,IPMASK=255.255.255.0,DEFRTR=172.22.87.2,MACADDRES S=000D56727245,BOOTRECORDTYPE1=FLASH,BOOTFILENAME1=15216EdfaSw_2.4.0,BOOTIPADDR1=0.0.0.0,B OOTRECORDTYPE2=TFTP,BOOTFILENAME2=bin/15216EdfaSw_2.3.0,BOOTIPADDR2=172.22.128.249,CLI=TL1 "
;

The cause could be either a corrupt or incomplete image, or an incorrectly addressed or named boot entry. First, check the entry address and file name using the RTRV-NE-GEN command.

Often, a corrupt file is caused by it not being FTP'd in binary mode. If this is possible, redownload the file using the instructions in the Release Notes, the "COPY-RFILE" section, or "File Transfers".

Sometimes, if the flash file system is full, the file may not download completely. See the "Image File Download Incomplete" section above.

10.2.5  Complete Boot Up Failure

If the primary image fails to boot, the ONS 15216 EDFA2 boots the second image. If both fail, the ONS 15216 EDFA2 continues to try to alternately boot the images unsuccessfully.

If this occurs, the cause could be either corrupt or incomplete images, or incorrectly addressed or named boot entries. Follow the instructions below to correct these problems.


Note If the ONS 15216 EDFA2 firmware is not version 2.3.14 or greater and the software has not been upgraded to 2.1.0 or greater, the CISCO15 user resets to read_write access level, not read_write_admin, which has full administrative control. Contact the Cisco TAC for assistance.



Step 1 Connect to the RS-232 (EIA/TIA-232) port.

Step 2 Open HyperTerminal. (HyperTerminal can be found in the Microsoft Windows Accessories menu.)

Step 3 While the dots are present in the HyperTerminal window during the reboot process, enter Ctrl C on the keyboard.

The ONS 15216 EDFA2 should boot from the firmware image. The prompt is %.

Step 4 At the hostname prompt, enter the following command within 60 seconds of rebooting:

hostname:edfaboot% login CISCO15
hostname:edfaboot% password

Step 5 At the hostname prompt, enter the following command:

hostname:edfaboot% ffs file list

Determine which image files are present. Ensure that there is enough space on the FFS for two images and that the images are complete. The 2.0.1 image should be 1,683,299 bytes, the 2.1.0 image should be 2,021,467 bytes, and the 2.2.1 image should be 1,963,195 bytes. See the 2.3.0 Release Notes for the 2.3.0 image file size. Use the ffs file delete command to remove any unwanted files as needed. Use the network host ftp command to download new images as needed.

Step 6 At the hostname prompt, enter the following command:

hostname:edfaboot% srom cfg boot display

Check that the entries are complete and accurately reflect the image file names. Use the srom cfg boot modify command to correct the boot entries as needed.

Step 7 When the problems with the images and boot entries have been completed, enter the following command:

hostname:edfaboot% processor reset

The ONS 15216 EDFA2 should boot up properly. If not, use this procedure again to correct any remaining problems.


10.2.6  No Response from RS-232 Port

If the ONS 15216 EDFA2 does not respond when connected to the RS-232 (EIA/TIA-232) port, check that the physical connection is good, that power is supplied to the unit (POWER LED is on or flashing), that the DB-9 pinout is correct (see the "PC Connection via Modem" section), that the port speed and communications configuration are correct (see the "Serial Connection Procedure" section), and that any terminal server settings (if used) are correct.

10.2.7  No Response from LAN Port

If the ONS 15216 EDFA2 does not respond on the RJ-45 LAN port, check that the physical connection is good, that power is supplied to the unit (POWER LED is on or flashing), that the IP address and subnet mask are correct (RTRV-NE-GEN command from RS-232 port), and that the application (Telnet) is trying to access the correct IP address.

To connect using the RS-232 port, see the "Serial Connection Procedure" section. Check the IP settings using RTRV-NE-GEN ( Example 10-6).

Check the two LAN port LEDs to be sure that there is a connection to the unit (the left Ethernet socket LED is on) and that traffic is flowing (the right Ethernet socket LED is on or flashing). If the unit is not booting correctly and is continuously resetting itself, you must us the RS-232 port to address the issue as detailed in the "Complete Boot Up Failure" section.

Example 10-6 Checking IP Settings

Amp01:ONS15216 EDFA2> RTRV-NE-GEN:AMP01::ALL::;

þAmp01 2004-03-17 00:37:40
M þall COMPLD
þ"EQPT:NAME=Amp01,IPADDR=10.7.4.113,IPMASK=255.255.255.0,DEFRTR=10.7.4.1,MACADDR=059a383d97 ,BOOTRECORDTYPE1=FLASH,BOOTFILENAME1=15216EdfaSw_2.3.0,BOOTIPADDR1=0.0.0.0,BOOTRECORDTYPE2 =TFTP,BOOTFILENAME2=users/misc/15216EdfaSw_2.1.0,BOOTIPADDR2=10.75.0.32,CLI=TL1"
;

10.2.8  LAN Port Activity LED Stays On

Release Notes 2.1.0, 2.2.1, and 2.3.0 Caveat CSCdx41604. Ethernet activity LED initialization.

Explanation    When powered up without an Ethernet cable, the activity light remains on.

Recommended Action    The Ethernet activity light works correctly when connected to the network.

10.2.9  Lost Password

If the root password for CISCO15 is lost, there is a procedure to reset it to regain full administrative control of the ONS 15216 EDFA2. The user must be connected to the ONS 15216 EDFA2 by serial communication, reset the power to the unit, and perform a series of commands within 60 seconds of rebooting, according to the following procedure. This procedure resets the default user password only; no other settings are affected.


Warning The ONS 15216 EDFA2 ceases its optical amplification function when power is off during this process. Traffic should be rerouted before this procedure begins.



Note If the ONS 15216 EDFA2 firmware is not version 2.3.14 or greater and the software has not been upgraded to 2.1.0 or greater, the CISCO15 user resets to read_write access level, not read_write_admin, which has full administrative control. Contact the Cisco TAC for assistance.



Step 1 Connect to the RS-232 (EIA/TIA-232) port.

Step 2 Open HyperTerminal. (HyperTerminal can be found in the Microsoft Windows Accessories menu.)

Step 3 Perform hard power reset of the ONS 15216 EDFA2 (disconnect and reconnect power).

Step 4 While the dots are present in the HyperTerminal window during the reboot process, enter Ctrl C on the keyboard.

The ONS 15216 EDFA2 should boot from the firmware image. The prompt is %.

Step 5 At the hostname prompt, enter the following command within 60 seconds of rebooting:

hostname:edfaboot% user passwd set CISCO15 default

Step 6 At the hostname prompt, enter the following command:

hostname:edfaboot% login CISCO15
Password =
<enter>

Step 7 At the hostname prompt, enter the following command:

hostname:edfaboot% processor reset

After the processor reset, the default CISCO15 login password will be the default (the Enter key).


10.3  Status Information Needed by Cisco TAC

To get the most from an interaction with the Cisco Technical Assistance Center (TAC), the status information of the ONS 15216 EDFA2 should be collected in advance.

The following commands should be issued, and pasted into a text file.

RTRV-INV::ALL:101;

RTRV-NE-GEN:::102;

RTRV-ALM-ALL:::103::;

RTRV-DWDM::ALL:104;

RTRV-EQPT::ALL:105;

RTRV-TH-DWDM::ALL:106::;

RTRV-TH-EQPT::ALL:107::;

If the TL1 shell is not active or working, the following ASH commands should be issued, and pasted into a text file.

ffs file list

srom id display

srom cfg display

srom cfg boot display

snmp table display local cerent15216EdfaSromIpMgmtGroup

snmp table display local entPhysicalEntry

snmp row display local cerent15216EdfaCfgGroup

snmp table display local cerent15216EdfaCommTrapEntry

snmp row display local cerent15216EdfaOverallStatusGroup

snmp table get local cerent15216EdfaAlarmEntry

snmp table get local cerent15216EdfaPumpStatusEntry

snmp table get local cerent15216EdfaCfgGroup


hometocprevnextglossaryfeedbacksearchhelp

Posted: Sun Apr 2 01:38:27 PST 2006
All contents are Copyright © 1992--2006 Cisco Systems, Inc. All rights reserved.
Important Notices and Privacy Statement.