Use this appendix to determine the weight of your system if your floor loading requirements are critical. Table A-1 provides maximum system weights for estimating floor loading requirements.
Configuration | Weight | Floor Loading | Area |
---|---|---|---|
Nonredundant | 85-100 lb. (38.25-45 kg) | 34.69-40.82 lb/ft2 (173.86-204.55 kg/m2) | 2.45 ft2 (.22 m2) |
Redundant | 100-157 lb. (45-70.65 kg) | 40.82-64.08 lb/ft2 (204.55-321.14 kg/m2) | 2.45 ft2 (.22 m2) |
Table A-2 lists weights of various VCO/4K components. This table does not include the following OEM-supplied equipment:
Refer to the specifications supplied with this equipment for their weights and dimensions.
Component | Weight in Pounds | Weight in Kilograms |
---|---|---|
System enclosure | 26.69 | 12.01 |
Front door | 10.06 | 4.53 |
Fan unit | 6 | 2.70 |
AC power supply module | 15.72 | 7.07 |
DC power supply module | 18.34 | 8.25 |
Card Type |
|
|
AAC | 1.20 | 0.57 |
CPA/DRC24 | 1.80 | 0.82 |
Combined Controller | 3.84 | 1.73 |
CPU | 1 | 0.45 |
Storage/Control I/O Module | 2.31 | 1.04 |
D&I | 1.91 | 0.86 |
ICC | 2.07 | 0.95 |
16-Span I/O Module for ICC | 1.12 | 0.51 |
IPRC | 2.21 | 1.00 |