cc/td/doc/product/mels/cm1500
hometocprevnextglossaryfeedbacksearchhelp
PDF

Table Of Contents

System Configuration

Required Materials

Connections to the NEMI

Serial Connection

Ethernet Connection

Logging into the NEMI

System Configuration

16 Channel Configuration

netconfig Command Options

Keymap Settings

Time Zone and Time Synchronization Settings

Date Settings

Network Configuration

NEMI Serial Communication Settings

Simple Network Management Protocol Configuration

Information Options

Restore Options

NEMI 32 Channel Configuration

Software Maintenance Overview

Rebooting the NEMI

Emergency Password Reset

Software Updates


System Configuration


This chapter describes system configuration procedures for both the 16- and 32-channel systems. Included are the requirements and procedures for the physical connections of the hardware and the configuration of the network connection using the NEMI. This chapter includes the following sections:

Required Materials

Connections to the NEMI

Logging into the NEMI

System Configuration

netconfig Command Options

NEMI 32 Channel Configuration

Software Maintenance Overview

Software Updates


Note Each NEMI must be configured separately for the specific operating environment. The configuration is done using the NEMI interfaces.



Note Either a serial port or an ethernet port can be used to log into the NEMI and configure the system. Only configure one port at a time, so in case of mistakes, the other (unchanged) port can be used to correct any settings.


Required Materials

The following is required to configure the NEMI:

A laptop computer with an RS-232 port, an appropriate serial communications program (HyperTerminal), and one LapLink cable.

or

A laptop computer with a 10BaseT ethernet card and one ethernet crossover cable (X-Cable).

See Appendix A, "Cables and Cabling" for details on the cables that are used with the NEMI and DEMI modules.

Connections to the NEMI

This section describes the two types of NEMI connections:

Serial Connection

Ethernet Connection

Serial Connection

To connect a laptop computer to the NEMI you should use a LapLink cable. This cable contains all serial signals and has the handshake signals crossed. See Appendix A, "Cables and Cabling" for complete cable specifications.

Almost any serial communications program can be used, as long as it can be set to support the factory-default configuration. You can use HyperTerminal, available with Windows 95/98.

The following instructions assume the modem is connected to the COM2 or COM4 port, leaving the COM1 and COM3 ports available for the LapLink cable.

To connect a laptop computer to the NEMI, follow these steps:


Step 1 Connect one end of the LapLink cable to the NEMI and the other end to the laptop on COM1.

Step 2 Start the HyperTerminal application. Enter a name and icon for the new connection. Select the outgoing communication port. In our example it would be "Direct to Com1" because that is the port to which we connected the cable.

The default settings are 19.2 kbps, 8 bits, no parity, 1 stop bit, hardware flow control. Cisco recommends using 9600 baud. Save these settings for future use.

Step 3 Open the connection and determine if the connection is successful.


If the NEMI is powered on, the cable is connected properly with the NEMI DB9 linked to the laptop DB9, and the serial line port settings are correct, you should see the Linux login greeting:

unknown login

A NEMI serial connection is shown in Figure 4-1. Next, proceed to the "Logging into the NEMI" section.

Figure 4-1 NEMI Serial Connection

Ethernet Connection

The NEMI's ethernet address is set by default to 192.168.168.168 and the subnet mask is set to 255.255.255.0. Follow these steps to connect to the NEMI using an ethernet connection:


Step 1 Connect the computer's ethernet interface to the NEMI using an ethernet X-Cable (see Appendix A, "Cables and Cabling" for cabling specifications).

Step 2 Set the computer's IP network address to 192.168.168.xxx, where xxx is any value in the range from 1 to 254, except 168.

Step 3 In Windows 95/98, choose Start and then Run. Type the following command:

telnet 192.168.168.xxx <Enter>

If the NEMI is powered on and the cable is connected properly you should see the Linux login greeting:

unknown login:

A NEMI ethernet connection is shown in Figure 4-2. Next, proceed to the "Logging into the NEMI" section.

Figure 4-2 NEMI Ethernet Connection

Logging into the NEMI

Once connected to the NEMI, you can log in as one of the following accounts: root, netadmin, or user.


Note The default password of all of these accounts is ChgMeNOW.To guarantee secure operation we recommend that you change the default passwords as soon as possible. You can change the passwords of your account using the passwd command.


User root can change the passwords for everybody. For example, to change the password for the netadmin user, type the following:

passwd netadmin

For administration we recommend using the netadmin account. System setup, typically done once per system, requires root privileges that are obtained with the super user (su) command. The su command prompts the user for the root password.

System Configuration

The following sections describe the configuration steps required for both the 16 and 32 Channel systems. The steps to configure the 32 Channel system are documented in the "NEMI 32 Channel Configuration" section.

16 Channel Configuration

The primary chassis of the 16 Channel system includes the NEMI module and the extension chassis contains the DEMI module. Both the NEMI and DEMI have to be interconnected using an external bus cable. In this configuration, only the NEMI is configured. Figure 4-3 shows the physical configuration of the
Cisco Metro 1500 series 16 Channel system and Figure 4-4 shows the software configuration steps flowchart.

Figure 4-3 Cisco Metro 1500 Series 16 Channel System Configuration

Figure 4-4 Cisco Metro 1500 Series 16 Channel System Configuration Steps Flowchart

netconfig Command Options

.To configure the NEMI you'll use the netconfig command as follows:

netconfig <Enter>

Depending on your terminal emulation (Telnet or Hyper Terminal), the screen output may be appear differently from one connection type to the other.


Note If your screen looks very different than those shown in the following figures, press the ESC Button to stop netconfig. For display purposes in this guide, all dialog box figures have been reversed. Printing technology generates dark characters on a white background, whereas terminal screens display light characters on a dark background.


Be sure that your screen windows are as large as possible. Change the terminal emulation of the NEMI by typing either TERM=vt100, TERM=linux, or TERM=ansi. The netconfig screens are best viewed with Microsoft's Telnet application using TERM=vt100. The netconfig Menu screen is shown in Figure 4-5.

Figure 4-5 netconfig Menu Screen

Keymap Settings

By default, the NEMI comes configured for a U.S. keyboard. Use the netconfig command to change the keyboard setting permanently if you are not operating in a U.S. language environment. See Figure 4-5 and Figure 4-6.

Figure 4-6 Example of Azerty Keyboard Map

It takes a few moments to load the keyboard mapping files. Once you have selected the appropriate keyboard map, use the netconfig test mode to verify that you have chosen the correct mapping.

If you have selected an incorrect keymap, use one of the following commands to correct the problem:

Enter loadkeys -d for the default map, but depending on the current keymap, it may be difficult to type the hypen (-).

Enter us for a QWERTY keyboard.


Note You must reboot the NEMI before the new keyboard settings take effect.


Time Zone and Time Synchronization Settings

The NEMI supports the Network Time Protocol (NTP). NTP synchronizes the time of a computer client or server to another server or reference time source. The time source can be a radio or satellite receiver or modem. NTP provides client accuracies typically within a millisecond on LANs and up to a few tenths of a millisecond on WANs relative to a primary server synchronized to Coordinated Universal Time (UTC) through a global positioning service (GPS) receiver. Typical NTP configurations utilize redundant servers and diverse network paths to achieve high accuracy and reliability. Some configurations include cryptographic authentication to prevent accidental or malicious protocol attacks.


Note Using the NTP for time zone and time synchronization is optional.


NTP has many options that depend on the time server setup. You need to be familiar with NTP, the Cisco Metro 1500 series system configuration, and the networking options to complete this setup.

To setup the NTP, follow these steps:


Step 1 Get the IP addresses of the installed time servers. For reliability, more than one time server should be active.

Step 2 Log into the NEMI as root and run the netconfig command. Choose Zone to define your local time zone. See Figure 4-7. Exit netconfig, but do not reboot.


Note You need to set your local time zone to get your local time.


Figure 4-7 Time-Zone Configuration

Step 3 Enter ntpdate x.x.x.x (where x.x.x.x is a time-server IP address) to set the NEMI clock to a time that is close to the actual time and to check the accuracy of the time server address.

Step 4 Enter pico -w /etc/ntp.conf to edit the ntpd configuration file and replace the x.x.x.x of the server lines with the correct IP addresses. Remove the comment character (#) for each line with a valid IP address.

Step 5 Edit the startup file if you want to start ntpd at power on. Enter pico -w /etc/rc.d/rc.inet2 and remove the comment character (#) for the if - fi section near the end of this file. This section starts ntpd.

Step 6 Write out the ntp.conf file by entering Ctrl-X Ctrl-Y.

Step 7 Reboot the system by entering reboot and wait for the ntpd to stabilize.


Date Settings

The NEMI sets the date and time using numbers only. To set the date and time, follow these steps:


Step 1 Log into the NEMI as root and run the netconfig command.

Step 2 Select the Date option.

Step 3 To set the date and time to 27 Feb. 9:55 a.m. 2000, enter 022709552000. The format is MMDDhhmmCCYY, where MM is month, DD is day, hh is hour, mm is minute, CC is century, and YY is year. See Figure 4-8.


Figure 4-8 Date and Time Setting Screen


Note You must reboot the NEMI before the new date settings take effect.


Network Configuration

To configure the NEMI for use on an IP network, ask your network administrator for the following information and fill in the blank form available in the
Cisco Metro 1500 Series Operations Guide:

Host names for the NEMIs

Domain name

Host IP addresses for both NEMIs

IP netmask

IP broadcast address

Gateway/router address

Domain name server address

Once you have the necessary information (see Appendix B, "IP Addresses") log into the NEMI using the netadmin account. Enter the su command to gain root privilege and use the Netconfig command from the netconfig main menu to enter the above values. This procedure configures the network side of the NEMI. See Figure 4-9 through Figure 4-15 for the configuration screens.

Figure 4-9 Enter Host Name Screen

Figure 4-10 Enter Domain Name Screen

Figure 4-11 Enter Local IP Address Screen

Figure 4-12 Enter Netmask Screen

Figure 4-13 Enter Gateway Address Screen

Figure 4-14 Select Nameserver Screen

Figure 4-15 Network Setup Complete Screen

Check your work carefully, and then enter the reboot command to have the new network settings take effect.

After this reboot, if the correct IP addresses and masks have been defined, the NEMI shows up on the network. To test the success of the NEMI network configuration, try to ping the NEMI from another computer that is connected to the same network as the NEMI.

For example, from a Windows 95/98 system, open a DOS window and enter the ping xx.xx.xx.xx command, where xx.xx.xx.xx is the Host IP address you entered during the network configuration of the NEMI. If you receive a time-out message, either the NEMIs ethernet settings are not correct or there is a hardware problem.

NEMI Serial Communication Settings

You can use the NEMIs serial port in three different ways:

1. Direct connection using a LapLink cable (factory default)

2. Dial-in using a modem (using PPP)

3. Direct PPP access over a leased line

Cisco recommends using PPP and a network protocol over the serial line at 9600 baud.

The following illustrations provide an overview of the process of configuring the serial settings. Select the ConSerial option from the netconfig menu screen to access these options.

Figure 4-16 Serial Settings Screen

Figure 4-17 Serial Speed Setup Screen

Figure 4-18 Serial Line Type Screen

Figure 4-19 PPP Usage Screen

If you dial-in with a modem or leased line, Cisco recommends using PPP. PPP establishes a network connection similar to an ethernet connection. You have to enter the IP addresses for both sides of the PPP connection and the netmask.

Figure 4-20 Remote IP Address Screen

The remote system can either be a terminal concentrator or a network management system which are connected to the other side of the PPP connection. Since PPP has only two stations on the network, the netmask can be automatically set by the computer. However, you can save address space by setting the subnet mask manually. See Figure 4-21 and Figure 4-22.

Figure 4-21 Netmask for PPP Screen

Figure 4-22 Enter Netmask for PPP Screen

For a typical configuration, the NEMIs Ethernet IP address should be different from the PPP IP address. However, it is possible to choose the same addresses for both interfaces.

Figure 4-23 Local PPP IP Address Screen

Figure 4-24 Enter Local PPP IP Address Screen

Simple Network Management Protocol Configuration

The NEMI can direct SNMP traps to a specific system if it is installed on a permanent network. To access SNMP options, select the TrapIP option from the netconfig main menu screen. You can also use the snmpconfig command to configure more than one system to receive traps or multiple systems to receive classes of traps. See Chapter 6, "Command Reference."

To change configuration files and other text-based files, the NEMI makes two text editors available, pico and vi. Pico is a member of the pine mail-kit. The mail-kit is not included with this product.

Pico has a very short learning curve because the most often used commands are displayed in the two bottom lines of the screen. For a printed short introduction and a screen shot of pico, see Chapter 6, "Command Reference."

To avoid line wrapping in pico, start pico using pico -w filename.

Information Options

To access the information screen, select Info from the netconfig main menu. The info screen ( Figure 4-25) shows the date, the keyboard map, the network settings, and the serial settings. Changes made by netconfig are shown in this menu. However, they will be only activated after a system reboot. The header line shows the netconfig version in use. In case of trouble with the NEMI, you should make sure that you have the latest available version.

Figure 4-25 NEMI Network Configuration Screen

Restore Options

The netconfig main menu screen provides three options to restore the system to previously saved configurations:

Restore—Provides options to access previously saved NEMI settings.

LapLink—Provides options to set LapLink options to the Cisco recommended value of 9600 baud.

Factory—Provides options to restore the system to its factory default settings.


Caution Use caution when accessing any of these restoration options. Failure to do so may result in an unusable system.

NEMI 32 Channel Configuration

The 32 Channel system consists of two 16 Channel systems, which are interconnected using a hidden network domain between two NEMIs. The NEMI in the primary chassis is called the NEMI-Master and the NEMI in extension chassis B is called the NEMI-Slave. This type of configuration is called an Inter-NEMI Network Connection (INNC). Figure 4-26 shows the physical configuration of the Cisco Metro 1500 series 32 Channel system and Figure 4-27 shows the software configuration steps flowchart.

Figure 4-26 Cisco Metro 1500 Series 32 Channel System Configuration

Figure 4-27 Cisco Metro 1500 Series 32 Channel System Software Configuration Flowchart

The 32 Channel system can be configured in two different ways:

1. Serial Inter-Connection between NEMI-Master and NEMI-Slave

2. Ethernet Inter-Connection between NEMI-Master and NEMI-Slave

The Cisco Metro 1500 series leaves the factory configured as a 16 channel system. To configure a 32 Channel system you need to link two 16 Channel systems (each with a NEMI) together through either their ethernet ports (using an ethernet X-Cable) or by linking their serial ports using a LapLink cable.


Note See Appendix A, "Cables and Cabling" for cabling specifications.


In a serial inter-connection, serial connections to both NEMIs are used for network management or service. In an Ethernet inter-connection, you can use the two free 10BaseT ports for these same tasks. The NEMI connected to the LAN is called the NEMI-Master and the NEMI used for service and configuration is called the NEMI-Slave.

The following configuration steps need to be repeated for both NEMIs:

1. Creation of the /etc/.ResetNemiConfiguration file

2. Use of netconfig to complete the configuration

After successful configuration and connection of both NEMIs, both systems exchange their data via the INNC and the same information is available on both systems. The two 16 channel systems that were separate, now appear to be a single 32 Channel system.

To achieve this task, the INNC needs a four address block of IP addresses out of a network address range. These addresses must not be used locally and cannot be routed.


Note The NEMI-Master uses the default address +1 of this block, whereas the NEMI-Slave uses the default address +2. The first and last addresses are reserved.


The /etc/.ResetNemiConfiguration file prepares the configuration process and reboots the NEMI. The netconfig option (after the reboot) displays the following screens, collects settings for the INNC and then branches into basic 16-channel netconfig mode.

To start the process, you need to login as root. After doing so, type the following:

/etc/.R<TAB><ENTER>

Hitting the TAB-Key after the R invokes filename recognition and since there is only one filename, which starts with .R in the directory /etc, you will see the following:

/etc/.ResetNemiConfig

The Enter key starts execution of this program.

The ResetNEMIConfig file (as its name implies) resets the default 16 Channel configuration and allows you to define a new (in this case) 32 Channel configuration. This program reboots the NEMI. After the reboot, log in again as root and type the following:

netconfig

The first screen to appear is the NEMI Setup screen. See Figure 4-28. Select Yes to begin a 32 Channel configuration.

Figure 4-28 NEMI Setup Screen One

The next screen asks if you are working with a NEMI-Master or a NEMI-Slave. See Figure 4-29.

Figure 4-29 NEMI Setup Screen Two

You'll need to go through this sequence once while being logged in on the NEMI-Master and once again while being logged in on the NEMI-Slave.

Figure 4-30 NEMI 32 Channel Master Setup Screen One

At this stage you need to decide what type of INNC to use. It has to be the same type for both the NEMI-Master and NEMI-Slave. It can be either serial (as in this example), or 10BaseT.

Figure 4-31 NEMI 32 Channel Master Setup Screen Two

Next, enter the IP address range for the INNC. See Figure 4-32.

Figure 4-32 Enter NEMI 32 Channel Master Start of IP Address Screen

Record the block of IP addresses. They need to be the same for both the NEMI-Master and the NEMI-Slave. The program chooses the right address for each NEMI according to NEMI type. Next, enter the netmask of the NEMI. See Figure 4-33.

Figure 4-33 Enter NEMI Netmask

The NEMI 32 Channel Master Setup summary screen appears. See Figure 4-34. Look it over carefully and confirm your configuration options by selecting Yes.

Figure 4-34 NEMI 32 Channel Master Setup Summary Screen

You are now returned to the INNC netconfig menu screen. See Figure 4-35 and the "netconfig Command Options" section.

Figure 4-35 NEMI 32 Channel Master Serial Inter-Conn Setup Screen

These steps are the same as configuring a 16 Channel system. However, if the INNC uses the serial port, the serial menu entry is not displayed. Similarly, if the INNC uses the ethernet port, the Ethernet menu does not appear.

Software Maintenance Overview

The following sections provide information on various software maintenance issues that may arise while using the Cisco Metro 1500 series system.

Rebooting the NEMI

The NEMI may be rebooted using one of the following procedures:

1. Normal/Orderly reboot

Log in using the root account and password. From the command line, issue the reboot command. This will result in an orderly shutdown and restart of the NEMI operating system. The optical systems are not affected by this type of reboot.

2. Hardware Reset

The hardware reset button is recessed in a small hole located on the NEMI module just below the bus interconnect ports at the bottom of the NEMI module. Insert a small pointed object to depress the Reset button and reboot the NEMI. The optical systems are not affected by this type of reboot.

Emergency Password Reset

Security within the Linux operating system is robust. Since the Cisco Metro 1500 series system can supply a sizable portion of network bandwidth to the enterprise; security is a major concern. However, situations do arise when one of the access passwords to the system is not readily available, but access needs to be provided as soon as possible.

For these reasons, the system offers a password reset option that will return all passwords to their factory defaults.

To reset the factory passwords, follow these steps:


Step 1 Connect a computer to the chosen access port (either ethernet or serial) and use a small pointed object to reset the NEMI.

Step 2 Count the beeps of the NEMI during reboot (one from the BIOS and two pairs at the start of a 20 second time window) for a total of five beeps.

Step 3 After the fifth beep, login into the system using the following account and password:

account: Maint
password: ChgMeNOW

Be aware of upper and lower case sensitivity. Successful logging into the Maint account results in a pair of triple beeps and a reboot. Once rebooted, the system passwords are reset to their factory default values.

Password Reset Restrictions and Caveats

All logins are logged by the system. Restarts are also logged and transmitted using SNMP. The Maint account is only open for a window of 20 seconds after the last beep. Any attempt before or after that time will lead to standard UNIX procedures for handling wrong passwords or illegal logins (next login is delayed).

Therefore, you need to wait until the last beep to avoid system delays. It might take several attempts to complete this procedure. Only passwords are reset to factory defaults. All other settings and performance of the optical transmission systems are unaffected. This procedure does not interrupt optical traffic.

Cisco recommends that you personalize the NEMI passwords as soon as possible to minimize possible exposure. This is true even if the endpoints of the optical network are within the physical security zone. You want to restrict access to the NEMI to keep system security (and thereby system stability) high.

Software Updates

See the "Downloading a System Update" section on page C-1 for information on downloading and installing system software upgrades as they become available.


hometocprevnextglossaryfeedbacksearchhelp

Posted: Tue Apr 26 06:01:01 PDT 2005
All contents are Copyright © 1992--2005 Cisco Systems, Inc. All rights reserved.
Important Notices and Privacy Statement.