cc/td/doc/product/dsl_prod/c6130ni2/userdoc
hometocprevnextglossaryfeedbacksearchhelp
PDF

Table of Contents

Installing a Direct Connect with a POTS Splitter Configuration
Installation Checklist
Installation Procedures

Installing a Direct Connect with a POTS Splitter Configuration


This chapter provides installation procedures for Direct Connect with a POTS splitter configuration.


Warning Only trained and qualified personnel should be allowed to install, replace, or service this equipment.


Caution   Before you start the installation procedures, read the entire chapter for important information and safety warnings.


Note   Before installing and cabling the equipment, be aware of standard safety practices and the hazards involved in working with electrical circuitry to prevent accidents. See the "Safety Requirements" section for all cautions and warnings that are necessary to ensure a safe and hazard-free installation.

To see translations of the warnings that appear in this publication, refer to the Regulatory Compliance and Safety Information for the Cisco 6100 Series System document.


Tip See the "Direct Connect with a POTS Splitter Configuration" section for more information about Direct Connect with a POTS splitter configuration components.

Installation Checklist

When you install a Direct Connect with a POTS splitter configuration, be sure that you follow the installation procedures in the proper sequence. Table 3-1 is a checklist of the installation steps in the order in which they should occur. Detailed installation instructions are located in the sections following Table 3-1.


Caution   Proper ESD protection is required whenever you handle Cisco digital subscriber line access multiplexer (DSLAM) equipment. Installation and maintenance personnel should be properly grounded using ground straps to eliminate the risk of ESD damage to the equipment. Cards are subject to ESD damage whenever they are removed from the chassis.

Table 3-1   Installation Checklist—Direct Connect with a POTS Splitter Configuration

Check Installation Procedure

 

1. Stabilize and measure the rack space.

 

2. Install the POTS splitter(s) in the rack.

 

3. Install the fan tray in the rack.

 

4. Install the thermal guard on the Cisco 6100 chassis.

 

5. Install the Cisco 6100 chassis in the rack.

 

6. Install the blank faceplates in the open slots.

 

7. Ground the Cisco 6100 chassis, fan tray, and POTS splitter.

 

8. Connect the Cisco 6100 chassis to the POTS splitter.

 

9. Attach the Cisco 6100 power connections to the fuse and alarm panel.

 

10. Attach the fan tray power connections to the fuse and alarm panel.

 

11. Locate or install the system I/O card on the backplane of the Cisco 6100.

 

12. Connect the fan tray to the Cisco 6100 chassis.

 

13. Connect the alarm contacts.

 

14. Connect the POTS splitter to the MDF1.

 

15. Pull all of the line cards away from the backplane connection (applicable if any line cards ship in the chassis).

 

16. Set the DIP switches to the OFF position.

 

17. Install the rear cover (optional).

 

18. Apply power to the system.

 

19. Verify that the fan tray is operational.

 

20. Install the NI-2 card.

 

21. Install the jumper card.

 

22. Reseat all of the line cards (applicable if any line cards ship in the chassis).

 

23. Install the cards in the Cisco 6100 and Cisco 6120 chassis, ATU-C line cards first.

 

24. Connect the NI-2 card to the network.

 

25. Install a subtended network (optional).

 

26. Connect the software management system to the Cisco 6100.

 

27. Connect a console terminal.

 

28. Connect the auxiliary port (optional).

 

29. Verify that the Cisco 6100 front cover is closed.

 

30. Close the optional rear cover.

 

31. Complete initial configuration.
1MDF = main distribution frame

Installation Procedures

The following sections detail the installation procedures for in a Direct Connect with a POTS splitter configuration.

Stabilize and Measure Rack Space

For the rack to remain stable, you must install your Cisco 6100 with NI-2 system from the bottom to the top of the rack. Before you install any of the chassis, measure the total rack space required to install your system. The required rack space depends on the number of Cisco 6100 chassis, fan trays, and POTS splitters you plan to use. The number of chassis and required fan trays increase if you plan to install a subtended network.

You can install a combination of the Cisco 6100 system components in a 7-foot rack:


Note    In a Direct Connect with a POTS splitter configuration using a Cisco 6120 and quad-port flexi ATU-C line cards (4xflexis), it is necessary to install an additional Cisco 6120 chassis. The additional Cisco 6120 chassis expands the system to accommodate 128 ports.

The Cisco 6100 with NI-2 system fits in a 23-inch wide rack. See Table 2-2 for individual rack space requirements. Allow 1 rack unit (RU) of space between the fan tray and the POTS splitter. This space allows for the intake plenum and for cabling back to front for the NI-2 card.


Warning To prevent bodily injury when mounting or servicing this unit in a rack, you must take special precautions to ensure that the system remains stable. The following guidelines are provided to ensure your safety:

—This unit should be mounted at the bottom of the rack if it is the only unit in the rack.

—When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack.

—If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack.

If you plan to expand your system to include more chassis in the future, allow space in the rack for additions during the initial installation, keeping in mind the weight distribution and stability of the rack.

Install the POTS Splitter

You can use the following POTS splitters in a Direct Connect with POTS splitter configuration:

The following sections detail the installation procedures for each POTS splitter.

Install the Cisco 6120

Complete the following steps to install the Cisco 6120 in the rack:


Warning Two people are required to lift the chassis. Grasp the chassis underneath the lower edge and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back.


Note   The Cisco 6120 chassis ships with a retaining bar in place. Verify that the retaining bar is secure before lifting the chassis. The retaining bar prevents the cards from falling out of the chassis.


Step 1   Position one Cisco 6120, which occupies 4 RUs of space, at the bottom of the rack.

The Cisco 6120 does not dissipate heat; therefore, the bottom of the rack is the best location for the Cisco 6120.

Step 2   Use six mounting screws and a Phillips-head screwdriver to bolt the Cisco 6120 in the rack.

Step 3   Remove the retaining bar.

Step 4   Repeat Steps 1 through 3 for each Cisco 6120 as necessary.

See Figure 1-1 for the correct placement of the Cisco 6120.



Install the Third-Party POTS Splitter

Refer to the appropriate vendor documentation for installation procedures for the third-party POTS splitter.

See Figure 1-1 for the correct placement of the third-party POTS splitter.


Warning Two people are required to lift the chassis. Grasp the chassis underneath the lower edge and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back.

Install the Fan Tray

Complete the following steps to install the fan tray in the rack:


Note   If you are using more than one Cisco 6100 chassis in a Direct Connect with a POTS splitter configuration, you must install a fan tray under each chassis.


Step 1   Place the fan tray chassis on a flat and stable surface (for example, a table top).

Step 2   Locate the first fan module and unscrew the thumbscrew that holds the fan module in place (the screw at the top of each fan module), as shown in Figure 3-1.


Figure 3-1   Fan Tray Thumbscrews


Step 3   Carefully remove the fan module by pulling it toward you. The fan module is located on slide rails for easy removal and installation. (See Figure 3-2.)


Figure 3-2   Removing the Fan Module from the Fan Tray


Step 4   Place the fan module on a flat and stable surface (for example, a table top) until you are ready to reinsert it into the fan tray.

Step 5   Repeat Steps 2 through 4 for each fan module.

Step 6   Position the fan tray chassis, which occupies 2 RUs of space, above the POTS splitter.

Allow an additional 1 RU of space between the fan tray and the POTS splitter. This space allows for the intake plenum.

Step 7   Use four mounting screws and a Phillips-head screwdriver to bolt the fan tray in the rack above the POTS splitter. See Figure 1-1 for the correct placement of the fan tray.

Step 8   Align a fan module with the fan tray slide rails inside the fan tray.

Step 9   Slide the fan module into the fan tray.

Step 10   Tighten the thumbscrew above the fan module.

Step 11   Repeat Steps 8 through 10 for each fan module.


Note   For information about fan tray maintenance and air filter replacement, see "Upgrading and Maintaining the Cisco 6100 System."



Install the Thermal Guard on the Cisco 6100

A thermal guard is required when using the Cisco 6100 chassis with 4xflexis.


Warning Two people are required to lift the chassis. Grasp the chassis underneath the lower edge and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back.

Complete the following steps to install the thermal guard on the Cisco 6100 chassis:


Step 1   Place the Cisco 6100 chassis on a stable surface (for example, a table top).

Step 2   Angle the thermal guard above the chassis, as shown in Figure 3-3.


Figure 3-3   Thermal Guard Angle Over Cisco 6100


Step 3   Place the lip of the thermal guard under the lip of the Cisco 6100 chassis.

Step 4   Gently push the back of the thermal guard onto the chassis.

Step 5   Use six screws (three on each side of the chassis) to secure the thermal guard to the chassis, as shown in Figure 3-3.

Figure 3-4 shows an installed thermal guard.


Figure 3-4   Thermal Guard Installed on Cisco 6100 Chassis




Install the Cisco 6100 Chassis

Complete the following steps to install the Cisco 6100 chassis:


Warning Two people are required to lift the chassis. Grasp the chassis underneath the lower edge and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back.


Note   If the Cisco 6100 chassis ships with any line cards installed, verify that the chassis front cover is secure before lifting the chassis. The front cover prevents the line cards from falling out of the chassis.


Step 1   Position one Cisco 6100, which occupies 9 RUs of space, above the fan tray. The bottom of the Cisco 6100 chassis should be flush with the top of the fan tray.

Step 2   Use four mounting screws and a Phillips-head screwdriver to bolt the Cisco 6100 in the rack.

Step 3   Remove the chassis front cover.

Step 4   Repeat Steps 1 through 3 for each Cisco 6100 as necessary.

See Figure 1-1 for the correct placement of the Cisco 6100.



Install Blank Faceplates

Blank faceplates should occupy any empty slots in either the Cisco 6100 or the Cisco 6120 chassis. The blank faceplate installation is similar to the line card installation.

Complete the following steps to install the blank faceplates in the Cisco 6100 or Cisco 6120:


Step 1   Vertically align the blank faceplate edge with the guides at the top and bottom of the slot.

Step 2   Lift up on the ejector tab and gently apply pressure to the bottom of the faceplate while pushing the blank faceplate into the slot.

Step 3   Push on the faceplate to fully seat the blank faceplate.

Step 4   Press down on the ejector tab to secure the faceplate.



Ground the Cisco 6100, Fan Tray, and POTS Splitter

During the system installation, complete the following steps to connect the grounding lug on the Cisco 6100, fan tray, and POTS splitter directly to the rack:


Step 1   Remove all paint or oxidation from the rack at the point of the grounding connection.

Step 2   Measure enough wire to connect the Cisco 6100 to the rack. Use 12 American Wire Gauge [AWG] or thicker (green or green with yellow stripes) stranded copper wire for the Cisco 6100 chassis grounding. Use 14 AWG or thicker (green or green with yellow stripes) stranded copper wire for the fan tray and POTS splitter grounding. (See Figure 3-5 for grounding wire location.)


Tip Make sure your wire is as short as possible to make the connection.

Step 3   Use a wire stripper to remove the casing from both ends of the wires.

Step 4   Use a 3/16-inch flat-head screwdriver to loosen the screw on the rack.

Step 5   Hook one end of the copper wire around the screw on the rack.

Step 6   Tighten the rack screw over the copper wire.

Step 7   Use a flat-head screwdriver to loosen the compression screw that is provided on the grounding lug of the Cisco 6100.

The grounding lugs are located in the upper left corner of each chassis (viewed from the rear), as shown in Figure 3-5.

Step 8   Insert the other end of the copper wire under the compression screw.

Step 9   Tighten the compression screw over the copper wire.

Step 10   Repeat Steps 1 through 9 for the fan tray and the POTS splitter (Cisco 6120).

Refer to the appropriate vendor documentation for grounding procedures for the third-party POTS splitter.


Note    Do not ground the components in a rack by chaining them together.

The left side of Figure 3-5 shows how to ground the Cisco 6100, fan tray, and POTS splitter to the rack.


Figure 3-5   Grounding the Cisco 6100, Fan Tray, and POTS Splitter




Connect the Cisco 6100 to the POTS Splitter

You can use the following POTS splitters in a Direct Connect with POTS splitter configuration:

The following sections detail the cabling procedures to connect the Cisco 6100 to each POTS splitter. These connections are for xDSL data flow between the Cisco 6100 and the POTS splitter.

Connect the Cisco 6100 to the Cisco 6120

Connect the one-to-two Champ cables from the Cisco 6100 (connectors J39 through J44) to the Cisco 6120 (connectors J1 through J6). Table 3-2 shows the corresponding Cisco 6100 and Cisco 6120 connectors when two Cisco 6120 chassis are used.


Note   See the "Cisco 6100 to Cisco 6120 Cables" section for cable part numbers.

Table 3-2   Cisco 6100 and Cisco 6120 Corresponding Connectors

Cisco 6100 Connector First
Cisco 6120 Connector
Second
Cisco 6120 Connector

J39

J3

J3

J40

J1

J1

J41

J5

J5

J42

J4

J4

J43

J2

J2

J44

J6

J6

Figure 3-6 shows the cabling between one Cisco 6100 and two Cisco 6120 chassis in which the one-to-two cables are used.


Figure 3-6   Cisco 6100 to Two Cisco 6120 Chassis Cabling Diagram with One-to-Two Cables



Note    For additional information about the Cisco 6120 backplane connectors, see the "Cisco 6120 Backplane" section on page 1-30.

Connect the Cisco 6100 to the Third-Party POTS Splitter

Use the cables described in the "Cisco 6100 to Third-Party POTS Splitter Cables" section to cable the Cisco 6100 to the third-party POTS splitter. Refer to the appropriate vendor documentation for cabling procedures for the third-party POTS splitter.

Attach Cisco 6100 Power Connections


Caution   To prevent the system from powering up, do not install the fuses at this time. If the fuses are already installed in the fuse and alarm panel, remove them. You can replace the fuses after the system is installed and connected.

External power is supplied to the system as -48 VDC from the central office (CO) power source or rectifier to the fuse and alarm panel. Power is fed from the fuse and alarm panel to the Cisco 6100 chassis by a terminal block connector with four dual-power connections (P13) located at the top of the chassis backplane. Figure 3-7 shows the location of the power connection (P13) on the chassis.


Note   The fuse and alarm panel and wires are not provided by Cisco.


Figure 3-7   Cisco 6100 Power Connection Locations


You can wire the power connections from the Cisco 6100 to the fuse and alarm panel for either dual- or single-power feed.


Note   Connect each Cisco 6100 with NI-2 system component to a separate fuse. Do not power the components in the rack by chaining them together.

See "Preparing for Installation" for the calculation tables that are necessary to determine the minimum fuse rating for each component that is wired to the fuse and alarm panel. Refer to the power rating label on the back of the Cisco 6100 to determine the maximum fuse rating.

Attach Cisco 6100 Power Connections for a Dual-Power Feed

Complete the following steps to attach the Cisco 6100 power connections (P13) to the fuse and alarm panel for a dual-power feed:


Step 1   Use a socket driver or a Phillips-head screwdriver to remove the clear cover over the Cisco 6100 power connections.

Step 2   Measure enough wire (12 AWG black and red copper solid or stranded wire) to connect each of the Cisco 6100 power input connections to the fuse and alarm panel.

Figure 3-8 shows the Cisco 6100 power input connections wired to the fuse and alarm panel.


Figure 3-8   Power Input Connections for the Cisco 6100—Dual-Power Feed



Note    Figure 3-8 shows the wires looped through a ferrite. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.

Step 3   Use a wire stripper to remove the casing from both ends of the wires.

Step 4   Use a Phillips-head screwdriver to attach a wire to the -48V_A power input connection on the Cisco 6100 (P13).

Step 5   Loop the wire through the ferrite as shown in Figure 3-9. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.


Note    Looping the wire secures the ferrite.


Figure 3-9   Wire Looped through Ferrite


Step 6   Attach the wire to a fuse and alarm panel NEG (negative) DC connector.

Step 7   Use a Phillips-head screwdriver to attach a wire to the -48V_B power input connection on the Cisco 6100 (P13).

Step 8   Loop the wire through the ferrite as shown in Figure 3-9. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.

Step 9   Attach the wire to a fuse and alarm panel NEG DC connector.

Step 10   Measure enough wire (12 AWG black and red copper solid or stranded wire) to connect each of the Cisco 6100 power return connections to the fuse and alarm panel.

Figure 3-10 shows the Cisco 6100 power return connections wired to the fuse and alarm panel for a dual-power feed.


Figure 3-10   Power Return Connections for the Cisco 6100—Dual-Power Feed



Note    Figure 3-10 shows the wires looped through a ferrite. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.

Step 11   Use a wire stripper to remove the casing from both ends of the wires.

Step 12   Use a Phillips-head screwdriver to attach a wire to a -48V power return connection (-48RTN) on the Cisco 6100 (P13).

Step 13   Loop the wire through the ferrite as shown in Figure 3-9. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.

Step 14   Attach the wire to a fuse and alarm panel POS (positive) RTN connector.

Step 15   Repeat Steps 10 through 14 for the remaining -48V power return connection (-48RTN).

Step 16   Use a socket driver or a Phillips-head screwdriver to attach the clear cover over the Cisco 6100 power connections.



Attach Cisco 6100 Power Connections for a Single-Power Feed

Complete the following steps to attach the Cisco 6100 power connections (P13) to the fuse and alarm panel for a single-power feed:


Step 1   Use a socket driver or a Phillips-head screwdriver to remove the clear cover over the Cisco 6100 power connections.

Step 2   Measure enough wire (12 AWG black and red copper solid or stranded wire) to connect each of the Cisco 6100 power connections to the fuse and alarm panel.

Figure 3-11 shows the Cisco 6100 power connections wired to the fuse and alarm panel for a single-power feed.


Figure 3-11   Power Connections for the Cisco 6100—Single-Power Feed



Note    Figure 3-11 shows the wires looped through a ferrite. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.

Step 3   Use a wire stripper to remove the casing from both ends of the wires.

Step 4   Use a Phillips-head screwdriver, to attach a wire to the -48V_A power input connection on the Cisco 6100 (P13).

Step 5   Loop the wire through the ferrite as shown in Figure 3-12. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.


Note    Looping the wire secures the ferrite.


Figure 3-12   Wire Looped through Ferrite


Step 6   Attach the wire to the fuse and alarm panel NEG DC connector.

Step 7   Use a Phillips-head screwdriver to attach a wire to a -48RTN power return connection on the Cisco 6100 (P13). See Figure 3-11 for correct placement.

Step 8   Loop the wire through the ferrite as shown in Figure 3-12. If you use thicker wire, it will not be necessary to loop the wire through the ferrite.

Step 9   Attach the wire to the fuse and alarm panel POS RTN connector. See Figure 3-11 for correct placement.

Step 10   Use a Phillips-head screwdriver to attach a wire to connect the -48V_A and -48V_B power input connections to each other.

Step 11   Use a Phillips-head screwdriver to attach a wire to connect the -48RTN power return connections to each other.

Step 12   Use a socket driver or a Phillips-head screwdriver to attach the clear cover over the Cisco 6100 power connections.



Attach Fan Tray Power Connections


Caution   To prevent the system from powering up, do not install the fuses at this time. If the fuses are already installed in the fuse and alarm panel, remove them. You can replace the fuses after the system is installed and connected.

External power is supplied to the system as -48 VDC from the CO power source or rectifier to the fuse and alarm panel. Power is fed from the fuse and alarm panel to the fan tray by a terminal block connector with four dual power connections (P1) located at the top of the fan tray backplane. Figure 3-13 shows the location of the power connection (P1) on the fan tray.


Note   The fuse and alarm panel and wires are not provided by Cisco.


Figure 3-13   Fan Tray Power Connection Location



Note   Connect each Cisco 6100 with NI-2 system component to a separate fuse. Do not power the components in the rack by chaining them together.

See "Preparing for Installation" for the calculation tables that are necessary to determine the minimum fuse rating for each component that is wired to the fuse and alarm panel. Refer to the label on the back of the fan tray to determine the maximum fuse rating.

You can wire the power connections from the fuse and alarm panel to the fan tray for either dual- or single-power feed.

Attach Fan Tray Power Connections for a Dual-Power Feed

Complete the following steps to attach the fan tray power connections to the fuse and alarm panel for a dual-power feed:


Step 1   Use a socket driver or a Phillips-head screwdriver to remove the clear cover over the fan tray power connections.

Step 2   Measure enough wire (14 to 18 AWG copper solid or stranded wire) to connect each of the fan tray power connections to the fuse and alarm panel.

Figure 3-14 shows the power connections from the fan tray to the fuse and alarm panel for a dual-power feed.


Figure 3-14   Power Connections for the Fan Tray—Dual-Power Feed


Step 3   Use a wire stripper to remove the casing from both ends of the wires.

Step 4   Use a Phillips-head screwdriver to attach a wire to the -48VA power input connection on the fan tray (P1).

Step 5   Attach the wire to the fuse and alarm panel NEG DC connector. See Figure 3-14 for correct placement.

Step 6   Use a Phillips-head screwdriver to attach a wire to the -48VB power input connection on the fan tray (P1).

Step 7   Attach the wire to the fuse and alarm panel NEG DC connector. See Figure 3-14 for correct placement.

Step 8   Use a Phillips-head screwdriver to attach a wire to an RTN power return connection on the fan tray (P1).

Step 9   Attach the wire to a fuse and alarm panel POS RTN connector.

Step 10   Repeat Steps 8 and 9 for the remaining RTN power return connection.

Step 11   Use a socket driver or a Phillips-head screwdriver to attach the clear cover over the fan tray power connections.



Attach Fan Tray Power Connections for a Single-Power Feed

Complete the following steps to attach the fan tray power connections to the fuse and alarm panel for a single-power feed:


Step 1   Use a socket driver or a Phillips-head screwdriver to remove the clear cover over the fan tray power connections.

Step 2   Measure enough wire (14 to 18 AWG copper solid or stranded wire) to connect each of the fan tray power connections to the fuse and alarm panel.

Figure 3-15 shows the power connections from the fan tray to the fuse and alarm panel for a single-power feed.


Figure 3-15   Power Connections for the Fan Tray—Single-Power Feed


Step 3   Use a wire stripper to remove the casing from both ends of the wires.

Step 4   Use a Phillips-head screwdriver to attach a wire to the -48VA power input connection on the fan tray (P1).

Step 5   Attach the wire to the fuse and alarm panel NEG DC connector.

Step 6   Use a Phillips-head screwdriver to attach a wire to an RTN power return connection on the fan tray (P1). See Figure 3-15 for correct placement.

Step 7   Attach the wire to the fuse and alarm panel POS RTN connector. See Figure 3-15 for correct placement.

Step 8   Use a Phillips-head screwdriver to attach a wire to connect the -48VA and -48VB power input connections to each other.

Step 9   Use a Phillips-head screwdriver to attach a wire to connect the RTN power return connections to each other.

Step 10   Use a socket driver or a Phillips-head screwdriver to attach the clear cover over the fan tray power connections.



Locate or Install the System I/O Card

The Cisco 6100 chassis should ship with the system I/O card already installed on the chassis backplane. The system I/O card is attached to chassis connectors P3 and P9, two 2-mm hard metric (HM) module connectors.

If the system I/O card is missing from the Cisco 6100, complete the following steps to install it on the chassis backplane:


Step 1   Locate the twelve backplane screws shown in Figure 3-16. Use a Phillips-head screwdriver to remove the backplane screws. Keep these backplane screws for use when you install the system I/O card.


Figure 3-16   Backplane Screw Location for System I/O Card Installation


Step 2   Use a one-quarter inch socket driver or wrench to screw ten standoff screws into the locations formerly occupied by ten of the twelve screws that you removed in Step 1. Tighten the standoff screws using the one-quarter inch socket driver or wrench. See Figure 3-17 for standoff screw location.


Figure 3-17   Standoff Screw Location for System I/O Card Installation



Caution   Be careful when you remove the screws and reinsert the standoff screws into the screw holes on the backplane so that the backplane circuitry does not become damaged.

Step 3   Hold the system I/O card vertically and align the holes on the system I/O card over the twelve standoff screws, as shown in Figure 3-18.


Figure 3-18   System I/O Card Installation


Step 4   Carefully press the system I/O card onto the Cisco 6100 connectors P3 and P9 on the chassis backplane until the system I/O card is in place and against the standoff screws.

Step 5   Use a Phillips-head screwdriver and four backplane screws to attach the system I/O card to the standoff screws, as shown in Figure 3-18.

Step 6   Use a Phillips-head screwdriver and two backplane screws to attach the EMI cover bracket, as shown in Figure 3-19.


Figure 3-19   EMI Cover Installation


Step 7   Attach the EMI cover on the EMI fence, as shown in Figure 3-19.


Caution   Be careful not to bend the tabs on the EMI cover when you install the cover on the EMI fence.

Step 8   Verify that no EMI cover tabs are outside the EMI fence.

Step 9   Use a Phillips-head screwdriver and a screw to attach the EMI cover to the EMI cover bracket, as shown in Figure 3-19.

Step 10   Use a Phillips-head screwdriver and three backplane screws to attach the safety shield to the left side of the system I/O card, as shown in Figure 3-20. The backplane screws will screw into the existing standoff screws on the backplane.


Figure 3-20   Safety Shield and ESD Shield Installation


Step 11   Use a one-quarter inch socket driver or wrench to screw a standoff screw between relays K4 and K5, as shown in Figure 3-20. Tighten the standoff screws using the one-quarter inch socket driver or wrench.

Step 12   Place the ESD shield above the standoff screw that you installed in Step 10 so that the hole in the shield aligns with the standoff screw, as shown in Figure 3-20.

Step 13   Use a Phillips-head screwdriver and three backplane screws to attach the plastic ESD shield to the system I/O card (see Figure 3-20).



Connect the Fan Tray

Complete the following steps to connect the fan tray alarm cable:


Step 1   Attach the P1 connector of the fan tray alarm cable (part number 72-2086-01) to connector P2 on the fan tray backplane, as shown in Figure 3-21.

Step 2   Attach the P2 connector of the same fan tray alarm cable to connector P4 on the system I/O card, as shown in Figure 3-21.


Figure 3-21   Cabling the Fan Tray to the Cisco 6100




Connect the Alarm Contacts

Five rows of wire-wrap pins are located on the right side of the system I/O card. These pins support the following alarms:

One NI-2 card in the Cisco 6100 chassis manages the alarms that are generated by the wire-wrap pins (P1 through P5). An alarm cutoff (ACO) switch, located on the NI-2 card faceplate, shuts off the audible alarms.

Figure 3-22 shows the location of the wire-wrap pins on the system I/O card.


Figure 3-22   System I/O Card Alarm Contacts


Table 3-3 maps the wire-wrap pins to the alarms that are supported by the NI-2 card through the Cisco 6100 chassis backplane.

Table 3-3   System I/O Card Wire-Wrap Pin Mapping

PIN No. Header P1 Header P2 Header P3 Header P41 Header P5

Pin 1 (left)

AUD2_CRIT3_CO4

AUD_MIN5_CO

VIS6_MAJ_CO

DOOR ALARM

RX_BITS7_TIPA

Pin 2

AUD_CRIT_NO8

AUD_MIN_NO

VIS_MAJ9_NO

Reserved

RX_BITS_RINGA

Pin 3

AUD_CRIT_NC10

AUD_MIN_NC

VIS_MAJ_NC

Reserved

RX_BITS_GND/GND

Pin 4

AUD_MAJ_CO

VIS_CRIT_CO

VIS_MIN_CO

Reserved

RX_BITS_TIPB

Pin 5

AUD_MAJ_NO

VIS_CRIT_NO

VIS_MIN_NO

ACO11_NO

RX_BITS_RINGB

Pin 6 (right)

AUD_MAJ_NC

VIS_CRIT_NC

VIS_MIN_NC

ACO GND12

RX_BITS_GND/GND

1Header P4 is used for the fan tray alarm.

2AUD = audible.

3CRIT = critical.

4CO = common.

5MIN = minimum.

6VIS = visual.

7RX_BITS = receive building-integrated timing source.

8NO = normally open.

9MAJ = major.

10NC = normally closed.

11The ACO switch is located on the faceplate of the NI-2 card. This switch turns off the audible alarms that are generated by the system software.

12GND = ground.

Connect the POTS Splitter to the MDF

The following sections detail the cabling procedures to connect the POTS splitter to the MDF. You can use one of the following POTS splitters:

Connect the Cisco 6120 to the MDF

Complete the following steps to connect the Cisco 6120 to the MDF:


Step 1   Connect the xDSL subscriber line connectors (J11 to J14) to the MDF using the cables that are orderable through Cisco (see the "POTS Splitter to MDF Cables" section) or cables that are built according to the specifications for a Nortel NT-T100 series cable.

Step 2   Connect the voice lines by connectors (J7 to J10) to the MDF for distribution to the Public Switched Telephone Network (PSTN). Figure 3-23 shows the connectors used to link the Cisco 6120 to the Class 5 switch (through the MDF).


Figure 3-23   Cisco 6120 Connection to the MDF



Note    See the "Direct Connect with a POTS Splitter Configuration Port Mapping Tables" section for port mapping information.



Connect the Third-Party POTS Splitter to the MDF

Use the cables that are described in the "POTS Splitter to MDF Cables" section to cable the third-party POTS splitter to the MDF. Refer to the appropriate vendor documentation for cabling procedures for the third-party POTS splitter.

Pull All Line Cards Away

If the Cisco 6100 ships with any line cards installed, complete the following steps to pull the line cards away from the chassis backplane connection:


Caution   If the power connections are improperly connected and power is applied while the line cards are installed, the line cards and chassis could be damaged.


Step 1   Unlock any 4xflexi, as necessary.

Use a flat-head screwdriver to move the locking tab from the locked to the unlocked position. Be sure to turn the locking tab so that it does not overlap the 4xflexis, as shown in Figure 3-24.


Figure 3-24   Unlocking the 4xflexi


Step 2   Lift up on the ejector tab of each line card. This action disconnects the line card from the backplane.

Step 3   Carefully slide the line card toward you and away from the backplane connection.

Step 4   Repeat Steps 1 through 3 for each 4xflexi. Repeat Step 2 and Step 3 for the blank faceplates in the Cisco 6100 chassis.


Note    The NI-2 card and jumper card should not be installed in the chassis at this time.



Set DIP Switches

Set all DIP switches on SW1 and SW2 to the OFF position (Figure 3-25). The dip switches are located in the lower left corner of the backplane, as shown in Figure 1-5.


Warning Systems using a Cisco 6100 chassis must connect to the network through a POTS splitter.


Figure 3-25   xDSL Protection DIP Switches (in OFF position)


Install the Rear Cover

Complete the following steps to install the optional rear cover:


Step 1   Locate and remove six of the backplane screws that are currently used to hold the Cisco 6100 backplane to the chassis.

Three screws are located on the right of the chassis, and three are located on the left. See Figure 3-26 for the location of the screws. Keep the backplane screws. They will be used when you install the cover-mounting brackets.


Figure 3-26   Backplane Screws for Rear Cover Installation


Step 2   Install the six standoff screws in the locations formerly occupied by the six screws that you removed in Step 1. Use a one-quarter inch socket driver or wrench to tighten the standoff screws.

Step 3   Face the rear of the chassis and install the cover-mounting bracket on the right side of the chassis. Place the bracket over the standoff screws. Use three of the screws that you removed in Step 1 to fasten the cover-mounting bracket to the chassis. (See Figure 3-27.)


Figure 3-27   Installing the Cover-Mounting Bracket


Step 4   Install the cover-mounting bracket (with the rear cover attached) on the left side of the chassis. Place the bracket (with rear cover) over the standoff screws. Use three of the screws that you removed in Step 1 to fasten the cover-mounting bracket (with rear cover) to the chassis.

Step 5   Use the tie wraps provided in the accessory kit to attach cables to the cover-mounting bracket loops, as necessary.



Apply Power

Complete the following steps to apply power to the Cisco 6100 with NI-2 system:


Step 1   Verify that there are no line cards installed in any of the Cisco 6100 chassis.

Step 2   Apply power to the system with one of the following methods:


Caution   If the power connections are improperly connected and power is applied while the cards are installed, the cards and chassis could be damaged.

Step 3   Verify that the fuse calculation for the Cisco 6100 with NI-2 system is correct. See Table 2-4 for a fuse calculation table.

Step 4   Verify that the power connections from the Cisco 6100 to the fuse and alarm panel are wired as shown in Figure 3-10 or Figure 3-11.

Step 5   Verify that the power connections from the fan tray to the fuse and alarm panel are wired as shown in Figure 3-14 or Figure 3-15.

Step 6   Check the polarity of the -48 VDC connections to each chassis by attaching a voltmeter with the minus lead on -48RTN and the plus lead on -48V_A or -48V_B. Ensure that the meter reads between -36 VDC and -60 VDC. If your voltmeter shows a positive voltage, the power inputs might be reversed. If the voltmeter shows a negative voltage that is out of the -36 VDC to -60 VDC range, check the power supply for failure or check for a blown fuse in the fuse and alarm panel.



Verify Fan Tray Operation

Verify that the fan modules are operational by locating the LED on the front of each fan module. If the LED is

The fan modules should be operational before you install the line cards.


Caution   It is important that the Cisco 6100 cooling fans run continuously.

Install the NI-2 Card


Caution   Proper ESD protection is required each time you handle Cisco DSLAM equipment. Installation and maintenance personnel should be properly grounded using ground straps to eliminate the risk of ESD damage to the equipment. Cards are subject to ESD damage each time they are removed from the chassis.


Caution   Installing the cards in the chassis with the power leads reversed can damage the cards.


Warning The power supply circuitry for the Cisco DSLAM equipment can constitute an energy hazard. Before you install or replace the equipment, remove all jewelry (including rings, necklaces, and watches). Metal objects can come into contact with exposed power supply wiring or circuitry inside the DSLAM equipment. This could cause the metal objects to heat up and cause serious burns or weld the metal object to the equipment.


Warning Do not reach into a vacant slot or chassis while you install or remove a card or a fan. Exposed circuitry could constitute an energy hazard.


Note   All cards must be fully seated in the chassis. A push on the faceplate of each card is required for the card to be fully seated.

Complete the following steps to install the NI-2 card in the Cisco 6100. It is important that you accomplish each step completely before moving on to the next step.


Step 1   Inspect the NI-2 card. Verify that the daughterboard is fully seated on the main board.

Step 2   Verify that slots 10 and 11 of the Cisco 6100 chassis have no bent pins.

Step 3   Vertically align the card edge with the card guides at the top and bottom of slot 10 on the Cisco 6100.

Step 4   Lift up on the ejector tabs and gently apply pressure to the bottom of the faceplate while pushing the card into the slot.

Step 5   Push on the faceplate of each card to fully seat the card.

Step 6   Press down on the ejector tabs to secure the card and connect it to the backplane.

Step 7   Lock both NI-2 card locking tabs.

Use a flat-head screwdriver to turn the locking tab so that it overlaps the NI-2 card to prevent inadvertent dislodging, as shown in Figure 3-28.


Figure 3-28   Locking the NI-2 Card


Step 8   Perform a software update if the STATUS LEDs on the NI-2 card is flashing.

Refer to the Configuration Guide for Cisco DSLAMs with NI-2 for software upgrade procedures.



Install the Jumper Card

Complete the following steps to install a jumper card in slot 12 of the Cisco 6100 chassis:


Step 1   Vertically align the jumper card edge with the card guides at the top and bottom of slot 12.

Step 2   Lift up on the ejector tab and gently apply pressure to the bottom of the faceplate while pushing the jumper card into the slot.

Step 3   Push on the faceplate to fully seat the jumper card.

Step 4   Press down on the ejector tab to secure the faceplate.



Reseat the Line Cards


Caution   Proper ESD protection is required each time you handle Cisco DSLAM equipment. Installation and maintenance personnel should be properly grounded using ground straps to eliminate the risk of ESD damage to the equipment. Cards are subject to ESD damage each time they are removed from the chassis.

If you pulled the line cards away from the Cisco 6100 chassis backplane in the "Pull All Line Cards Away" section, reseat the line cards to verify the power connection.

Complete the following steps to reseat all of the line cards. It is important that you accomplish each step completely before moving on to the next step.


Note   All line cards must be fully seated in the chassis. A push on the faceplate of each line card is required for the line card to be fully seated.


Step 1   Reseat the 4xflexis in the Cisco 6100.

    a. Lift up on the ejector tab and gently apply pressure to the bottom of the faceplate while pushing the line card into the slot.

    b. Push on the faceplate of each line card to fully seat the line card.

    c. Press down on the ejector tab to secure the line card and connect it to the backplane.

    d. Lock any 4xflexis.


Note    It is not necessary to lock the 4xflexis.

Use a flat-head screwdriver to turn the locking tab so that it overlaps the 4xflexi to prevent inadvertent dislodging. Figure 3-24 shows how to position the locking tab.

    e. Reseat the remaining 4xflexis using the same procedure.

Step 2   Verify that the STATUS LEDs on all line cards are solid green (where applicable).

This self-test procedure takes several minutes. If the STATUS LEDs are not green after the self-test, see "Troubleshooting," for troubleshooting procedures.

Step 3   Perform a software update if the STATUS LEDs on the 4xflexis are flashing.

Refer to the Configuration Guide for Cisco DSLAMs with NI-2 for software upgrade procedures.


Note   Blank faceplates should occupy any empty slots in the Cisco 6100. The blank faceplate installation is similar to the line card installation.



Install the Cards in the Cisco 6100 and POTS Splitter


Caution   Proper ESD protection is required each time you handle Cisco DSLAM equipment. Installation and maintenance personnel should be properly grounded using ground straps to eliminate the risk of ESD damage to the equipment. Cards are subject to ESD damage each time they are removed from the chassis.

If the Cisco 6100 ships without any line cards installed in the chassis, install the Cisco 6100 with NI-2 system cards in the following order to verify the power connection.


Caution   Installing the cards in the chassis with the power leads reversed can damage the cards.


Warning The power supply circuitry for the Cisco DSLAM equipment can constitute an energy hazard. Before you install or replace the equipment, remove all jewelry (including rings, necklaces, and watches). Metal objects can come into contact with exposed power supply wiring or circuitry inside the DSLAM equipment. This could cause the metal objects to heat up and cause serious burns or weld the metal object to the equipment.


Warning Do not reach into a vacant slot or chassis while you install or remove a card or a fan module. Exposed circuitry could constitute an energy hazard.


Note   All cards must be fully seated in the chassis. A push on the faceplate of each card is required for the card to be fully seated.

To install all of the cards, complete the following steps. It is important that you accomplish each step completely before moving on to the next step.


Step 1   Install the 4xflexis in the Cisco 6100.

    a. Vertically align the line card edge with the guides at the top and bottom of slot 1 on the Cisco 6100.

    b. Lift up on the ejector tab and gently apply pressure to the bottom of the faceplate while pushing the line card into the slot.

    c. Push on the faceplate of each line card to fully seat the line card.

    d. Press down on the ejector tab to secure the line card and connect it to the backplane.

    e. Lock the 4xflexis.


Note    It is not necessary to lock the 4xflexis.

Use a flat-head screwdriver to turn the locking tab so that it overlaps the 4xflexi to prevent inadvertent dislodging. Figure 3-24 shows how to position the locking tab.

    f. Install the remaining 4xflexis using the same procedure.

The 4xflexis are installed in slots 1 through 8, 13 through 28, and 31 through 38.

Step 2   Install the POTS splitter cards in the Cisco 6120.

    a. Vertically align the card edge with the guides at the top and bottom of slot 1 on the Cisco 6120.

    b. Lift up on the ejector tab and gently apply pressure to the bottom of the faceplate while pushing the card into the slot.

    c. Push on the faceplate of each card to fully seat the card.

    d. Press down on the ejector tab to secure the card and connect it to the backplane.

    e. Install the remaining POTS cards using the same procedure.

The POTS cards are installed in slots 1 through 10 and 13 through 22 of the Cisco 6120.


Note    Refer to the appropriate vendor documentation for POTS splitter card installation procedures for the third-party POTS splitter.

Step 3   Verify that the STATUS LEDs on all line cards are solid green (where applicable).

This self-test procedure takes several minutes. If the STATUS LEDs are not green after the self-test, see "Troubleshooting," for troubleshooting procedures.

Step 4   Perform a software update if the STATUS LEDs on the 4xflexis are flashing.

Refer to the Configuration Guide for Cisco DSLAMs with NI-2 for software upgrade procedures.


Note   Blank faceplates should occupy any empty slots in the Cisco 6100. The blank faceplate installation is similar to the line card installation.



Connect the NI-2 Card to the Network

This section provides installation procedures for the DS3 and OC-3c network connections.

DS3 Network Connection Installation

Complete the following steps to connect the DS3/2DS3 NI-2 card to the network:


Step 1   Verify that the DS3/2DS3 NI-2 card is installed in slot 10 of the Cisco 6100 chassis to ensure that the DS3/2DS3 NI-2 card connections are active.

The DS3/2DS3 NI-2 card connections are on the system I/O card, which is located on the backplane of the Cisco 6100 chassis. These connections attach to the ATM switch. Two 75-ohm DS3 Bayonet-Neill-Concelman (BNC) connectors are provided for DS3 transmit (J14) and receive (J12). See Figure 3-29 for the location of the DS3 BNC connectors.


Figure 3-29   DS3 Network Interface Connection


Step 2   Attach one end of a coaxial cable (type 734A, type 735A, or equivalent) to the transmit DS3 BNC connector (J14) for the system I/O card on the chassis backplane.

Step 3   Attach the end of the cable that you used in Step 2, which originates at the transmit DS3 BNC connector, to the ATM switch.

Step 4   Attach one end of a coaxial cable (type 734A, type 735A, or equivalent) to the receive DS3 BNC connector (J12) for the system I/O card on the Cisco 6100 backplane.

Step 5   Attach the end of the cable that you used in Step 4, which originates at the receive DS3 BNC connector, to the ATM switch.



OC-3c Network Connection Installation

Complete the following steps to connect the OC-3c/OC-3c NI-2 card to the network:


Warning Do not stare into the beam or view it directly with optical instruments.


Step 1   Verify that the OC-3c/OC-3c NI-2 card is in slot 10 of the Cisco 6100 chassis.

Step 2   Pull the OC-3c/OC-3c NI-2 card transmit and receive fiber-optic cables from the ATM switch through the 1 RU of space between the fan tray and the POTS splitter.

Step 3   Attach the receive cable from the ATM switch to the transmit connector in the inset on the faceplate of the OC-3c/OC-3c NI-2 card (trunk 1 interface connector TX). See Figure 3-30 for the OC-3c network interface connection location.


Figure 3-30   OC-3c Network Interface Connection


The transmit connector is the one closest to the top of the faceplate. The receive connector is closest to the bottom of the faceplate. The connector IDs are silkscreened inside the inset.

Step 4   Attach the transmit cable from the ATM switch to the receive connector in the inset on the faceplate of the OC-3c/OC-3c NI-2 card (trunk 1 interface connector RX). See Figure 3-30 for the OC-3c network interface connection location.

Step 5   Allow enough slack in the cable so that the fan tray can be opened and the fans can be maintained.

Step 6   Coil the fiber loosely within the 1 RU of space to take out slack.



Install a Subtended Network Configuration

If you are installing a subtended network with subtended node chassis to a subtending host chassis, complete the steps in the following sections. The following sections provide installation procedures for the DS3 and OC-3c subtended network configuration.

If you are not installing a subtended network, go to the "Connect the Software Management System to the NI-2 Card" section.


Note   For information on a subtended network configuration, see the "Subtended Network Configuration" section on.

Cable the DS3 Subtending Network Configuration

Coaxial connections for DS3 cabling are located on the system I/O card. The transmit and receive DS3 BNC connectors on the subtending host chassis system I/O card are connected to the transmit and receive DS3 BNC connectors on the subtended node chassis system I/O card.


Note   The system I/O card BNC cables are not provided by Cisco.

Complete the following steps to cable the system I/O card for subtending:


Step 1   On the subtending host chassis backplane, attach one end of a BNC cable to the transmit DS3 BNC connector (J10) on the system I/O card.

Step 2   On the first subtended node chassis backplane, attach the end of the BNC cable used in Step 1 to the receive DS3 BNC connector (J12) on the system I/O card.

Step 3   On the subtending host chassis backplane, attach one end of a BNC cable to the receive DS3 BNC connector (J8) on the system I/O card.

Step 4   On the first subtended node chassis backplane, attach the end of the BNC cable used in Step 3 to the transmit DS3 BNC connector (J14) on the system I/O card.

Step 5   On the subtending host chassis backplane, attach one end of a BNC cable to the transmit DS3 BNC connector (J6) on the system I/O card.

Step 6   On the second subtended node chassis backplane, attach the end of the BNC cable used in Step 5 to the receive DS3 BNC connector (J12) on the system I/O card.

Step 7   On the subtending host chassis backplane, attach one end of a BNC cable to the receive DS3 BNC connector (J4) on the system I/O card.

Step 8   On the second subtended node chassis backplane, attach the end of the BNC cable used in Step 7 to the transmit DS3 BNC connector (J14) on the system I/O card.

Figure 3-31 shows the cabling for a DS3 subtending network configuration.


Figure 3-31   Cabling for DS3 Subtending Configuration




Cable the OC-3c Subtending Network Configuration

For OC-3c subtending, the connections are made from the front of the subtending host chassis and the subtended node chassis. To cable the Cisco 6100 with NI-2 system for OC-3c subtending, complete the following steps:


Step 1   Locate the trunk 1 interface connectors (TX and RX) and the subtend 2 interface connectors (TX and RX) on the front of each OC-3c/OC-3c NI-2 card. See Figure 3-30 for connector location.

Step 2   Attach an OC-3c fiber-optic cable to the transmit (TX) subtend 2 interface connector in the inset on the faceplate of the OC-3c/OC-3c NI-2 card in the subtending host chassis.

Step 3   Attach the other end of the cable that you used in Step 2 to the receive (RX) trunk 1 interface connector in the inset on the faceplate of the OC-3c/OC-3c NI-2 card in the subtended node chassis.

Step 4   Attach an OC-3c fiber-optic cable to the receive (RX) subtend 2 interface connector in the inset on the faceplate of the OC-3c/OC-3c NI-2 card in the subtending host chassis.

Step 5   Attach the other end of the cable that you used in Step 4 to the transmit (TX) trunk 1 interface connector in the inset on the faceplate of the OC-3c/OC-3c NI-2 card in the subtended node chassis.

Figure 3-32 shows the subtending connections between two Cisco 6100 with NI-2 system chassis.


Figure 3-32   Cabling Diagram for OC-3c Subtending




Connect the Software Management System to the NI-2 Card

Connect both the 10BaseT RJ-45 port on the NI-2 card (ENET) and the Sun SPARCstation running the CDM management application to an Ethernet so that the Cisco 6100 and the management station can communicate. Figure 3-33 shows where to connect the Ethernet cable.


Warning The ports labeled "ENET," "CNSL," and "AUX" are safety extra-low voltage (SELV) circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage, avoid connecting the SELV circuit to the telephone network voltage (TNV) circuits.


TimeSaver Cisco recommends that you label each data cable at both ends to identify its destination.


Figure 3-33   ENET, CNSL, and AUX RJ-48C Receptacle Connectors on the NI-2 Card


Connect a Console Terminal

Connect a VT100-compatible terminal to the system console port on the NI-2 card (CNSL). Connect the terminal to a power source and set it up using the values that are shown in Table 3-4. Figure 3-33 shows where to connect the console cable.


Warning The ports labeled "ENET," "CNSL," and "AUX" are SELV circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage, avoid connecting the SELV circuit to the TNV circuits.

Table 3-4   Terminal Settings

Baud rate

9600 to 38400 kbps (transmit and receive)

Character size

8 bits

Parity

None

Stop bits

1

Flow control

None

Connect the Auxiliary Port


Note   This step is optional.

Connect a terminal, a modem, or another serial device to the RJ-45 auxiliary port on the NI-2 card (AUX). Figure 3-33 shows where to connect the auxiliary cable.


Warning The ports labeled "ENET," "CNSL," and "AUX" are SELV circuits. SELV circuits should be connected only to other SELV circuits. Because the DSL circuits are treated like telephone-network voltage, avoid connecting the SELV circuit to the TNV circuits.


TimeSaver Cisco recommends that you label each data cable at both ends to identify its destination.

Close the Cisco 6100 Front Cover

Verify that the Cisco 6100 front cover is attached to the chassis and closed (see Figure 3-34).


Figure 3-34   Cisco 6100 Front Cover Installation


Close the Rear Cover

Complete the following steps to close the optional rear cover:


Step 1   Lift the two latches on the rear cover (as shown in Figure 3-35) as you close the rear cover. The rear cover closes left to right (seen from the rear of the chassis).


Figure 3-35   Securing the Rear Cover with the Latches


Step 2   Release the latches after the rear cover is in place.

Step 3   Align the two thumbscrews that are located on the rear cover with two thumbscrew fasteners on the bracket (see Figure 3-36). Tighten the thumbscrews to secure the rear cover.


Figure 3-36   Securing the Rear Cover with Two Thumbscrews




Complete Initial Configuration

When you turn on the Cisco 6100 for the first time, an interactive dialog called the System Configuration Dialog appears on the console screen. The System Configuration Dialog guides you through the initial configuration process. (You can run the dialog at any time by entering the setup command in privileged EXEC mode.)

When you complete the dialog, the system displays the configuration command script that you have created. It then offers you three options:

[0] Go to the IOS command prompt without saving this config.
[1] Return back to the setup without saving this config.
[2] Save this configuration to nvram and exit.

If you enter 2, the configuration is saved and used. If you answer 0 or 1, the configuration you created is not saved. Enter 1 if you wish to discard the configuration and restart the System Configuration Dialog.

Before You Begin

Complete these steps before you run the System Configuration Dialog:


Step 1   Determine the IP address for the Ethernet interface.

Step 2   If you plan to configure in-band management, also determine the IP address for the ATM interface that will be used for in-band management (ATM0/0).

Step 3   Find out what the password strategy is for your environment. The System Configuration Dialog prompts you for three passwords, plus an SNMP community string. The three required password types are enable secret, enable, and virtual terminal.

Step 4   Choose a name for the Cisco 6100. (This step is optional.)



Using the System Configuration Dialog

When you power up a Cisco 6100 for the first time, you are offered the option of running the System Configuration Dialog. The System Configuration Dialog offers two configuration options: basic management setup and extended setup.

An example of the use of each option follows the "Interface Numbering" section. In each example, an arrow marks the point in the dialog where basic management setup and extended setup diverge.

Interface Numbering

The System Configuration Dialog and the command line interface use the following interface numbering scheme:

Basic Management Setup Example

This is the basic management setup example:

--- System Configuration Dialog ---
Would you like to enter the initial configuration dialog? [yes/no]: y
At any point you may enter a question mark '?' for help.
Use ctrl-c to abort configuration dialog at any prompt.
Default settings are in square brackets '[]'.
Basic management setup configures only enough connectivity
for management of the system, extended setup will ask you
to configure each interface on the system
Would you like to enter basic management setup? [yes/no]: y
Configuring global parameters:
Enter host name [DSLAM]:
The enable secret is a password used to protect access to
privileged EXEC and configuration modes. This password, after
entered, becomes encrypted in the configuration.
Enter enable secret: beansoup
The enable password is used when you do not specify an
enable secret password, with some older software versions, and
some boot images.
Enter enable password: beansoup
% Please choose a password that is different from the enable secret
Enter enable password: lab1
The virtual terminal password is used to protect
access to the router over a network interface.
Enter virtual terminal password:
% No defaulting allowed
Enter virtual terminal password: lab
Configure SNMP Network Management? [yes]: y
Community string [public]:
Current interface summary
Any interface listed with OK? value "NO" does not have a valid configuration
Interface IP-Address OK? Method Status Protocol
ATM0/0 unassigned NO unset up up
Ethernet0/0 unassigned NO unset up up
ATM0/1 unassigned NO unset down down
ATM0/2 unassigned NO unset down down
Enter interface name used to connect to the
management network from the above interface summary: Ethernet0/0
Configuring interface Ethernet0/0:
Configure IP on this interface? [yes]: y
IP address for this interface: 172.27.144.141
Subnet mask for this interface [255.255.0.0] :
Class B network is 172.27.0.0, 16 subnet bits; mask is /16
The following configuration command script was created:
hostname DSLAM
enable secret 5 $1$pR/1$0zH7ohDaUKNML3SC2.RF5.
enable password lab1
line vty 0 4
password lab
snmp-server community public
!
no ip routing
!
interface ATM0/0
no ip address
!
interface Ethernet0/0
no shutdown
ip address 172.27.144.141 255.255.0.0
!
interface ATM0/1
shutdown
no ip address
!
interface ATM0/2
shutdown
no ip address
!
end
[0] Go to the IOS command prompt without saving this config.
[1] Return back to the setup without saving this config.
[2] Save this configuration to nvram and exit.
Enter your selection [2]: 2
% Shutdown not allowed for ATM0/0.
Building configuration...
Use the enabled mode 'configure' command to modify this configuration.
Press RETURN to get started!
Extended Setup Example

This is the extended setup example:

--- System Configuration Dialog ---
Continue with configuration dialog? [yes/no]: yes
At any point you may enter a question mark '?' for help.
Use ctrl-c to abort configuration dialog at any prompt.
Default settings are in square brackets '[]'.
Basic management setup configures only enough connectivity
for management of the system, extended setup will ask you
to configure each interface on the system
Would you like to enter basic management setup? [yes/no]: no
First, would you like to see the current interface summary? [yes]: yes
Interface IP-Address OK? Method Status Protocol
ATM0/0 70.0.0.2 YES NVRAM up up
Ethernet0/0 172.27.32.156 YES NVRAM up up
ATM0/1 unassigned YES unset down down
ATM0/2 unassigned YES unset administratively down down
ATM18/0 unassigned YES unset initializing down
ATM18/1 unassigned YES unset initializing down
ATM18/2 unassigned YES unset initializing down
ATM18/3 unassigned YES unset initializing down
ATM21/0 unassigned YES unset administratively down down
ATM21/1 unassigned YES unset administratively down down
ATM21/2 unassigned YES unset administratively down down
ATM21/3 unassigned YES unset administratively down down
ATM26/0 unassigned YES unset down down
ATM26/1 unassigned YES unset down down
ATM26/2 unassigned YES unset down down
ATM26/3 unassigned YES unset down down
Configuring global parameters:
Enter host name [DSLAM]: sw-ni2-2
The enable secret is a password used to protect access to
privileged EXEC and configuration modes. This password, after
entered, becomes encrypted in the configuration.
Enter enable secret: lqb
The enable password is used when you do not specify an
enable secret password, with some older software versions, and
some boot images.
Enter enable password [lab]: lab
The virtual terminal password is used to protect
access to the router over a network interface.
Enter virtual terminal password [lab]:
Configure SNMP Network Management? [no]:
Configure IP? [yes]:
Configure IGRP routing? [yes]: no
Configuring interface parameters:
Do you want to configure ATM0/0 interface? [yes]:
Configure IP on this interface? [yes]:
IP address for this interface [70.0.0.2]:
Subnet mask for this interface [255.0.0.0] :
Class A network is 70.0.0.0, 8 subnet bits; mask is /8
Do you want to configure Ethernet0/0 interface? [yes]:
Configure IP on this interface? [yes]:
IP address for this interface [172.27.32.156]:
Subnet mask for this interface [255.255.0.0] :
Class B network is 172.27.0.0, 16 subnet bits; mask is /16
Do you want to configure ATM0/1 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM0/2 interface? [no]:
Do you want to configure ATM18/0 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM18/1 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM18/2 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM18/3 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM21/0 interface? [no]:
Do you want to configure ATM21/1 interface? [no]:
Do you want to configure ATM21/2 interface? [no]:
Do you want to configure ATM21/3 interface? [no]:
Do you want to configure ATM26/0 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM26/1 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM26/2 interface? [yes]:
Configure IP on this interface? [no]:
Do you want to configure ATM26/3 interface? [yes]:
Configure IP on this interface? [no]:
The following configuration command script was created:
hostname sw-ni2-2
enable secret 5 $1$12Lo$vGKa1wlRcNyw06j1bgGQd0
enable password lab
line vty 0 4
password lab
no snmp-server
!
ip routing
!
interface ATM0/0
ip address 70.0.0.2 255.0.0.0
!
interface Ethernet0/0
ip address 172.27.32.156 255.255.0.0
!
interface ATM0/1
no ip address
!
interface ATM0/2
shutdown
no ip address
!
interface ATM18/0
no ip address
!
interface ATM18/1
no ip address
!
interface ATM18/2
no ip address
!
interface ATM18/3
no ip address
!
interface ATM21/0
shutdown
no ip address
!
interface ATM21/1
shutdown
no ip address
!
interface ATM21/2
shutdown
no ip address
!
interface ATM21/3
shutdown
no ip address
!
interface ATM26/0
no ip address
!
interface ATM26/1
no ip address
!
interface ATM26/2
no ip address
!
interface ATM26/3
no ip address
!
end
[0] Go to the IOS command prompt without saving this config.
[1] Return back to the setup without saving this config.
[2] Save this configuration to nvram and exit.
Enter your selection [2]:2
Building configuration...
Use the enabled mode 'configure' command to modify this configuration.
Press RETURN to get started!

You have completed the installation process for the Cisco 6100.


hometocprevnextglossaryfeedbacksearchhelp
Posted: Tue Jan 28 06:31:58 PST 2003
All contents are Copyright © 1992--2002 Cisco Systems, Inc. All rights reserved.
Important Notices and Privacy Statement.