cc/td/doc/product/access/ap/ap_ts3
hometocprevnextglossaryfeedbacksearchhelp
PDF

Table of Contents

Cabling DC Fuse Panels in the Cisco AccessPath-TS
Integrated Access System

Connect the Internal Power Supplies to the DC Fuse Panels
Input Connection
Install the Fuses
Powering On the System
Troubleshooting DC Fuse Panel Installation

Cabling DC Fuse Panels in the Cisco AccessPath-TS
Integrated Access System


This chapter describes and illustrates the procedure for cabling the DC fuse panels after you mount them in an Cisco AccessPath-TS Integrated Access System.

The DC fuse panels accept two 50 amp, -48 VDC circuits of input power. Each panel can supply a total of 100 amps of steady-state output current.


Note      Your DC fuse panel might look slightly different, but its functionality is the same as the panel described and illustrated below. For example, grey DC fuse panels have input circuit breakers and black panels do not.



Figure 2-1   DC Fuse Panel—Front View



Warning Before working on equipment that is connected to power lines, remove jewelry (including rings, necklaces, and watches). Metal objects will heat up when connected to power and ground and can cause serious burns or weld the metal object to the terminals.


Warning Before performing any of the following procedures, confirm that there is no power DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position.

Connect the Internal Power Supplies to the DC Fuse Panels

The following steps explain how to connect the internal power supplies to the DC fuse panels:


Step 1   Confirm that the 2 main circuit breakers on every DC fuse panel is in the OFF position. The switches point away from each other in the OFF position.


Note Grey DC fuse panels have input circuit breakers and black panels do not.



Caution There are 2 sets of independent input DC power connectors and, on grey DC fuse panels, 2 separate circuit breakers on grey versions of the DC fuse panel. Each of the 2 circuit breakers on a grey DC fuse panel is associated with only 1 side of the panel and 1 group of 10 DC output connections.

Step 2   Cut sets of wires (1 red, 1 black) to the lengths specified in Step 6 through Step 12.


Note Red wires are positive (+) and black wires are negative (-).


Step 3   Remove about 0.25 inch of insulation from each end of the wire and tin both ends to confirm that the wire does not fray or cause a bad connection.


Warning When stranded wiring is required, use approved wiring terminations, such as closed-loop or spade-type with upturned lugs. These terminations should be the appropriate size for the wires and should clamp both the insulation and conductor.

Step 4   Connect a spade-type terminal lug to an end of each wire, as necessary.

The wires to the Access Server Shelves, System Controller, and the Router Shelf (or shelves) do not require terminal lugs at the shelf end of the wires.

Step 5   The following steps explain how to connect each shelf (see Figure 2-2):


Note Your DC fuse panel might look slightly different, but its functionality is the same as the panel described and illustrated below.



Figure 2-2   Wiring the DC Fuse Panels



Caution The illustration shows the DC fuse panel terminal block. Install each wire from the designated DC fuse panel terminal to the designated shelf location (terminal) using 14 gauge copper wire. The proper wiring sequence is positive to positive (line to +) and negative to negative (neutral to -). Route all power wiring away from all sharp edges and the interface cards on the Access Server shelves to avoid possible damage to the wires.

Connect the Failsafe/Console Management Shelf

Step 6   For either the single or dual router configuration, wire the Failsafe/Console Management Shelf as follows:

DC Power Termination DC Fuse Panel and Terminal 14 gauge wire spec

Failsafe/Console Management Shelf
Positive terminal
Negative terminal


1 - A4 return
1 - A4 equip


Red wire 34 in. (86 cm) long
Black wire 34 in. (86 cm) long

Connect the Switch Shelf

Step 7   For either the single or dual router configuration, wire the Switch Shelf as follows:

DC Power Termination DC Fuse Panel and Terminal 14 gauge wire spec

Switch Shelf
Power supply 1 positive terminal
Power supply 1 negative terminal
Power supply 2 positive terminal
Power supply 2 negative terminal


1 - A5 return
1 - A5 equip
1 - B4 return
1 - B4 equip


Red wire 94 in. (239 cm) long
Black wire 94 in. (239 cm) long
Red wire 110 in. (279 cm) long
Black wire 110 in. (279 cm) long

Connect the First Router Shelf (Single or Dual Router Configurations)

Step 8   For either the single or dual router configuration, wire the first Router Shelf as follows. In the dual router configuration, the first Router Shelf is the lower of the 2 router shelves.

DC Power Termination DC Fuse Panel and Terminal 14 gauge wire spec

Router Shelf 1
Power supply 1 positive terminal
Power supply 1 negative terminal
Power supply 2 positive terminal
Power supply 2 negative terminal


1 - A6 return
1 - A6 equip
1 - B5 return
1 - B5 equip


Red wire 79 in. (201 cm) long
Black wire 79 in. (201 cm) long
Red wire 91 in. (231 cm) long
Black wire 91 in. (231 cm) long

Connect the Second Router Shelf (Dual Router Configuration Only)

Step 9   For the dual router configuration, wire the second Router Shelf as follows. In the dual router configuration, the second Router Shelf is the upper of the 2 router shelves.

DC Power Termination DC Fuse Panel and Terminal 14 gauge wire spec

Router Shelf 2
Power supply 1 positive terminal
Power supply 1 negative terminal
Power supply 2 positive terminal
Power supply 2 negative terminal


1 - A7 return
1 - A7 equip
1 - B6 return
1 - B6 equip


Red wire 74 in. (188 cm) long
Black wire 74 in. (188 cm) long
Red wire 86 in. (218 cm) long
Black wire 86 in. (218 cm) long

Connect the Access Server Shelves

Step 10   For either the single or dual router configuration, wire the upper tier of Access Server Shelves (AS1 through AS6) as follows:

DC Power Termination DC Fuse Panel and Terminal 14 gauge wire spec

Access Server Shelf 1 (AS1)
Positive terminal
Negative terminal


1 - A1 return
1 - A1 equip


Red wire 36 in. (91 cm) long
Black wire 36 in. (91 cm) long

Access Server Shelf 2 (AS2)
Positive terminal
Negative terminal


1 - A2 return
1 - A2 equip


Red wire 39 in. (99 cm) long
Black wire 39 in. (99 cm) long

Access Server Shelf 3 (AS3)
Positive terminal
Negative terminal


1 - A3 return
1 - A3 equip


Red wire 46 in. (117 cm) long
Black wire 46 in. (117 cm) long

Access Server Shelf 4 (AS4)
Positive terminal
Negative terminal


1 - B1 return
1 - B1 equip


Red wire 55 in. (140 cm) long
Black wire 55 in. (140 cm) long

Access Server Shelf 5 (AS5)
Positive terminal
Negative terminal


1 - B2 return
1 - B2 equip


Red wire 63 in. (160 cm) long
Black wire 63 in. (160 cm) long

Access Server Shelf 6 (AS6)
Positive terminal
Negative terminal


1 - B3 return
1 - B3 equip


Red wire 68 in. (173 cm) long
Black wire 68 in. (173 cm) long

Step 11   For either the single or dual router configuration, wire the first 4 lower tier Access Server Shelves (AS7 through AS10) as follows:

DC Power Termination DC Fuse Panel and Terminal 14 gauge wire spec

Access Server Shelf 7 (AS7)
Positive terminal
Negative terminal


1 - A1 return
1 - A1 equip


Red wire 67 in. (170 cm) long
Black wire 67 in. (170 cm) long

Access Server Shelf 8 (AS8)
Positive terminal
Negative terminal


1 - A2 return
1 - A2 equip


Red wire 72 in. (183 cm) long
Black wire 72 in. (183 cm) long

Access Server Shelf 9 (AS9)
Positive terminal
Negative terminal


1 - A3 return
1 - A3 equip


Red wire 75 in. (191 cm) long
Black wire 75 in. (191 cm) long

Access Server Shelf 10 (AS10)
Positive terminal
Negative terminal


1 - A4 return
1 - A4 equip


Red wire 82 in. (208 cm) long
Black wire 82 in. (208 cm) long

Step 12   For the single router configuration, wire the other 2 Access Server Shelves (AS11 and AS12), if present, as follows:

DC Power Termination DC Fuse Panel and Terminal 14 gauge wire spec

Access Server Shelf 11 (AS11)
Positive terminal
Negative terminal


1 - A7 return
1 - A7 equip


Red wire 79 in. (201 cm) long
Black wire 79 in. (201 cm) long

Access Server Shelf 12 (AS12)
Positive terminal
Negative terminal


1 - B6 return
1 - B6 equip


Red wire 87 in. (221 cm) long
Black wire 87 in. (221 cm) long

Input Connection

The following steps explain how to connect input power to the DC fuse panels:


Step 1   Confirm that the system system is properly grounded.

The DC fuse panels require that a frame ground be placed on the actual frame ground stud on the system rack. Use a green 6-gauge wire to connect a ground to the frame ground stud located at the top (or bottom) right rear corner of the system rack. The frame ground should be grounded at the main input to the system system.


Warning This equipment is intended to be grounded. Ensure that the host is connected to earth ground during normal use.


Warning When installing the unit, the ground connection must always be made first and disconnected last.


Warning Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available.

A readily accessible two-pole disconnect device must be incorporated in the fixed wiring.

Step 2   Confirm that every AccessPath shelf is properly grounded.

Step 3   Connect the 14 AWG green ground wires from the earthing terminal of each shelf to the tap angles:

    (a). For each shelf, cut 10 in. of 14 AWG wire.

    (b). Remove 0.25 inch of insulation from an end of the 14 AWG wire.

    (c). Double-crimp a ring-lug to an end of the wire and connect it to the tap angle at the right of each shelf using a screw and lock washer.

    (d). Ground each shelf by securing the other end of its grounding wire to the earthing terminal of the shelf.

Step 4   Confirm that the main power circuit breakers are OFF at the building feed; lockouts are mandatory.

Step 5   Confirm that the 2 main circuit breakers on the DC fuse panel are in the OFF position. The switches point away from each other in the OFF position.


Caution There are 2 sets of independent input DC power connectors and 2 separate circuit breakers. Each of the 2 sets of input DC power connectors on the DC fuse panel is associated with only 1 side of the panel and 1 group of 10 DC output connections.

Step 6   Cut 2 sets of 6-gauge copper wires (2 white, 2 black) to the lengths necessary to reach the DC power source from the DC fuse panels when they are mounted in the system rack.


Note White wires are positive (+) and black wires are negative (-).


Step 7   Remove 0.5 inch of insulation from an end of every wire.

Step 8   Remove the DC input terminal connectors on the rear panel by first removing the plastic safety shield, then loosening both locking nuts on each connector.

Step 9   Solder the uninsulated end of each wire into the terminal connector so that no bare wire is exposed.

Step 10   Replace the terminals on the appropriate connectors (positive to positive and negative to negative) on the DC fuse panels and tighten both locking nuts, as shown in Figure 2-3.


Note Your DC fuse panel might look slightly different, but its functionality is the same as the panel described and illustrated below.



Figure 2-3   DC Fuse Panel—Input Feed Wiring


Step 11   Replace the plastic safety shield that covers the DC input connectors.

Step 12   After connecting 2 sets of input feed wires to each of the DC fuse panels, connect each 50-amp input feed connection to the DC power source. Confirm that the polarity of all connections is correct.

Install the Fuses

The following steps explain how to install the correct fuses in the correct positions:


Step 1   On DC fuse panels provided with circuit breakers, confirm that the 2 main circuit breakers on the DC fuse panel are in the OFF position. The switches point away from each other in the OFF position.


Caution There are 2 sets of independent input DC power connectors and 2 separate circuit breakers. Each of the 2 sets of input DC power connectors on the DC fuse panel is associated with only 1 side of the panel and 1 group of 10 DC output connections.

Step 2   Install individual GMT-style fuses as listed in Table 2-1 (Single Router Configuration) or Table 2-2 (Dual Router Configuration) to protect the system at the component level.


Caution When the fuse is correctly installed, the rating stamped on the fuse is upside down as shown in Figure 2-4. The fuse is keyed to prevent incorrect insertion; do not force it.


Note      Your DC fuse panel might look slightly different, but its functionality is the same as the panel described and illustrated below.



Figure 2-4   Fuse Installation


Step 3   Verify that you installed GMT-style fuses of the correct rated current in the correct locations, as specified in either Table 2-1 (for Single Router Configurations) or Table 2-2 (for Dual Router Configurations).

Step 4   After installing all the fuses correctly, continue with the procedure "Powering On the System."

Table 2-1   DC Fuse Panel Fuse Locations and Sizes (Single Router Configuration)

DC Power Termination DC Fuse Panel and Terminal Fuse Size

Access Server Shelf 1

1 — A1

GMT 7.5

Access Server Shelf 2

1 — A2

GMT 7.5

Access Server Shelf 3

1 — A3

GMT 7.5

Failsafe/Console Management Shelf

1 — A4

GMT 3

Switch Shelf, Power Supply 1

1 — A5

GMT 15

Router Shelf 1, Power Supply 1

1 — A6

GMT 15

Access Server Shelf 11

1 — A7

GMT 7.5

Access Server Shelf 4

1 — B1

GMT 7.5

Access Server Shelf 5

1 — B2

GMT 7.5

Access Server Shelf 6

1 — B3

GMT 7.5

Switch Shelf, Power Supply 2

1 — B4

GMT 15

Router Shelf 1, Power Supply 2

1 — B5

GMT 15

Access Server Shelf 12

1 — B6

GMT 7.5

Access Server Shelf 7

2 — A1

GMT 7.5

Access Server Shelf 8

2 — A2

GMT 7.5

Access Server Shelf 9

2 — A3

GMT 7.5

Access Server Shelf 10

2 — A4

GMT 7.5

Table 2-2   DC Fuse Panel Fuse Locations and Sizes (Dual Router Configuration)

DC Power Termination DC Fuse Panel and Terminal Fuse Size

Access Server Shelf 1

1 — A1

GMT 7.5

Access Server Shelf 2

1 — A2

GMT 7.5

Access Server Shelf 3

1 — A3

GMT 7.5

Failsafe/Console Management Shelf

1 — A4

GMT 3

Switch Shelf, Power Supply 1

1 — A5

GMT 15

Router Shelf 1, Power Supply 1

1 — A6

GMT 15

Router Shelf 2, Power Supply 1

1 — A7

GMT 15

Access Server Shelf 4

1 — B1

GMT 7.5

Access Server Shelf 5

1 — B2

GMT 7.5

Access Server Shelf 6

1 — B3

GMT 7.5

Switch Shelf, Power Supply 2

1 — B4

GMT 15

Router Shelf 1, Power Supply 2

1 — B5

GMT 15

Router Shelf 2, Power Supply 2

1 — B6

GMT 15

Access Server Shelf 7

2 — A1

GMT 7.5

Access Server Shelf 8

2 — A2

GMT 7.5

Access Server Shelf 9

2 — A3

GMT 7.5

Access Server Shelf 10

2 — A4

GMT 7.5

Powering On the System

The following steps explain how to power on the system:


Step 1   Confirm that the main power circuit breakers are OFF at the building feed.


Warning Do not work on the system or connect or disconnect cables during periods of lightning activity.


Warning Before performing any of the following procedures, confirm that power is removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position.

Step 2   Confirm that the 2 main circuit breakers on each of the DC fuse panels are in the OFF position. The switches point away from each other in the OFF position.


Note The grey DC fuse panels have input circuit breakers and the black panels do not.


Step 3   There are 2 sets of independent input power connectors and, on grey DC fuse panels, 2 separate circuit breakers. Each of the 2 sets of power connectors on a DC fuse panel is associated with only 1 side of the panel and 1 group of 10 DC output connections.

Step 4   Confirm that the main power feeds to the DC fuse panels are the correct polarity.

Step 5   Confirm that all connections from the DC fuse panels to the DC power supplies are the correct polarity.

Step 6   Turn OFF all DC power supplies at the component level.

Step 7   Go to the main circuit breakers off the input feeds and place the circuit breakers in the ON position.


Warning After wiring the DC fuse panel, remove the tape from the circuit breaker switch handle and reinstate power by moving the handle of the circuit breaker to the ON position.


Caution Power is now present on thesystem rack. Hazardous conditions exist; use caution.

Step 8   Turn on both of the DC fuse panel Main Power A circuit breakers.


Note The grey DC fuse panels have input circuit breakers and the black panels do not.


Step 9   Turn on the DC fuse panel Main Power B circuit breaker on panel 1 only.

Step 10   Turn on all DC power supplies at the component level.

Step 11   Check the power supplies and systems for power-on LED indications and airflow. Make this visual check inside the cabinet on each power supply and each system.

Troubleshooting DC Fuse Panel Installation

If a power system failure occurs, 1 or more DC fuses will open. In case of multiple failures, 1 or both of the main circuit breakers will trip, shutting down several units in the system system if not the entire system.

The following steps explain how to troubleshoot the system:


Step 1   Check the individual power supplies to determine if any supply has no LED power on indication or no airflow. If a fault condition occurs, remove all power by first turning OFF the 4 DC fuse panel circuit breakers (if provided), then turning OFF the main power circuit breakers.

When equipment installed in an system system rack fails because of overheating or power loss, try operating the equipment by itself. Power OFF other equipment in the rack (and in adjacent racks) to allow the failing unit maximum cooling air and clean power.

Step 2   Replace any defective fuse with a fuse of the correct rating.


Warning Never change fuses with live power present. Lethal currents are present on and in the DC fuse panels.


Caution Never use a larger fuse than what is specified for the individual locations. Refer to Table 2-1 or Table 2-2 for the correct fuse size for every location.

Step 3   Follow the power-on sequence of operations. See the section "Powering On the System".

Step 4   Verify that the proper LED power on indications are present and that airflow has resumed.


Caution If there is still no power applied to the component in question (that is, if no LED power on indication is present and/or there is no airflow), a qualified service person should be called to replace the power supply component.


hometocprevnextglossaryfeedbacksearchhelp
Posted: Wed Jan 22 04:40:08 PST 2003
All contents are Copyright © 1992--2002 Cisco Systems, Inc. All rights reserved.
Important Notices and Privacy Statement.