Enclosure and Power Installation

Enclosure and Power Installation

Parts Checklist

Before you install the system, verify that all of the required parts are present and in good condition. If anything is missing or damaged, report it to a StrataCom Order Administration.

IGX 8 Enclosure

Check the cabinet for the following inventory:

_____

For rack-mount systems, four permanent mounting brackets are present. Also, for installation purposes only, a pair of temporary mounting brackets and a temporary spacer bracket are present.

_____

The unit has the correct power type (AC or DC) and the factory-installed Power Entry Back Card (PE-BC). For DC-powered systems, DC Power Entry Modules (PEMs) are installed in the PE-BC. For AC systems, check for the power supply tray, correct power cord, and correct number of supplies.

IGX 16/32 Enclosures

Check the cabinet for the following inventory:

_____

[IGX 16/32] The unit has the correct number of card cages (1 or 2).

_____

The unit has the correct power type (AC or DC) and the factory-installed Power Entry Back Cards (PE-BC), one per shelf. For DC-powered systems, DC PEMs are factory-installed in each PE-BC. For an AC system, check for the power supply tray and correct number of power supplies and cables.

Plug-In Cards

Make sure all purchased cards are present. Check the number and type of cards shipped against the number and type of card purchased. In the following list, the column on the left lists the front cards. The column on the right lists the possible corresponding back cards.

____

Correct number and types of NPMs

____

One SCM

____

Correct number of NTMs

____

____

____

____

Correct number of BC-T1s

Correct number of BC-E1s

Correct number of BC-Y1s

Correct number of BC-SRs

____

Correct number of BTMs

____

____

Correct number of AIT-T3s

Correct number of AIT-E3s

____

Correct number of ALMs

____

____

Correct number of BC-UAI-1T3s

Correct number of BC-UAI-1E3s

____

Correct number and types of CVMs

____

____

____

Correct number of BC-E1s

Correct number of BC-J1s

Correct number of BC-T1s

____

Correct number of UFM-Cs

____

____

____

Correct number of UFI-8T1-DB15s

Correct number of UFI-8E1-DB15s

Correct number of UFI-8E1-BNCs

____

Correct number and types of FRMs (including FRM-2s)

____

____

____

____

____

Correct number of FRI-T1s

Correct number of FRI-E1s

Correct number of FRI-X.21s

Correct number of FRI-V.35

Correct number of FRI-2-X.21s

____

Correct number of FTMs

____

Correct number of FPCs

____

Correct number of HDMs

____

Correct number of SDIs

____

Correct number of LDMs

____

Correct number of LDIs

____

Correct number of ARMs

____

Correct number of ARIs

____

____

Blank faceplates for unused back card slots

An inventory list of the installed cards is shipped with the unit. The list includes each card's serial number, revision number, and slot number (serial and revision numbers are also found on the solder side of each card). Check for the presence of any other pieces on the shipping list. After verifying that the correct cards are present, tape a copy of the inventory list to the back of this manual.

Site Preparation

The site must satisfy the following requirements:

  The standalone IGX 8 requires a floor area 19.9 inches (50.5 cm) wide and 60 inches (180 cm.) deep. This depth allows for opening the front door. Sufficient clearance around the cabinet must also be provided for access to the front and back of the cabinet while the door is open. The rack-mount IGX 8 requires 24.44 inches of vertical space.
  The standalone IGX 16 or 32 requires a floor area 19.9 inches (50.5 cm) wide and 47 inches (119.4 cm) deep. This spacing lets you open the front door. Clearance around the cabinet must also allow access to the front and back of the cabinet while the door is open. The rack-mount IGX 16 requires 32 inches (81.3 cm) of vertical space. The rack-mount IGX 32 requires 55 inches (139.7 cm) of vertical space.
  In a rack-mount system, the mounting rail pattern follows an EIA standard of 56 inches or 32 rack-mount units. For displacement information for the IGX and other StrataCom components in the STRATM cabinet, refer to the appendix titled "Cisco Cabinet Dimensions."
  The IGX operating environment should be as follows:
  Temperature and humidity range: 0º to 40º C (32º to 104º F) for normal operation, 50º C for up to 72 hours. Up to 85% relative humidity, non-condensing.
  Shock: withstands 10 G, 10 ms. at 1/2 sine wave.
  Vibration: withstands 1/4 G, 20 to 500 Hz.
  For AC power use, an AC power source must be available within 6 feet (1.8 m) of the IGX. For systems using a DC source, StrataCom does not supply the DC power cord, so the user or installer determines the cord length and the distance to the DC source. The wire should be 10 to 12 AWG or 4 sq. mm.
  A fully loaded, AC-powered IGX 8 dissipates up to 3,500 BTUs (1 KW hour). A DC-powered IGX 8 can dissipate up to 2720 BTUs.
  A fully loaded, AC-powered IGX 16 dissipates up to 4300 BTUs (1 KW hour). A DC-powered IGX 16 can dissipate up to 3600 BTUs.
  A fully loaded, AC-powered IGX 32 dissipates up to 8600 BTUs (1 KW hour). A DC-powered IGX 32 can dissipate up to 6800 BTUs.
  A fully loaded IGX 8 can weigh up to 173 lbs (79 kgs). A fully loaded IGX 16 can weigh up to 250 lbs (112.5 kgs). A fully loaded IGX 32 can weigh up to 500 lbs. (225 kgs).

Note If you move a STRATM cabinet, do not push it at its sides. Push at the front or back.
  Raised flooring with sufficient under-floor space to house the cables is recommended.
  An IGX is either mounted in a rack or free-standing (in a stand-alone cabinet). The location of the IGX should accommodate the routing of the data cables and the termination of the telephone company's or common carrier's circuits.
  The IGX 8 has one mounted wrist strap at the front and one at the back of the cabinet. Personnel with access to the IGX 8 cards should put on a wrist strap before handling the cards. An IGX 16/32 does not come with an attached wrist strap.

Seismic Considerations

To provide some protection against seismic activity, the feet and wheels of the IGX stand-alone cabinets can be removed to permit the cabinet to be bolted to a concrete floor or to a structural member in the floor.

In STRATM cabinets, provisions are available for seismic anchoring. Holes exist in the upper and lower corners for 3/8" or 1/2" bolts. Also, an optional stability plate can be purchased with the STRATM cabinet. The stability plate is bolted to the floor, then the STRATM cabinet is bolted to the stability plate. The "STRATM Seismic Anchoring " section contains instructions for installing the seismic stability plate.

Safety Requirements

The following paragraphs contain general safety information and information on T1 and CEPT (E1) safety requirements.

General Requirements

Warning The following safety requirements must be observed:

Power and Grounding

This section lists the requirements that relate to electrical power and grounding. These requirements cover installations at Central Office (CO) and Private Enterprise locations.

Electrical Power for AC Units

An AC power source must be available within 6 feet (1.8 m) of the system and easily accessible. Before turning on the power, verify that the power supplied to the node comes from a dedicated branch circuit.

The receptacles into which the IGX plugs must be of the grounding type. The grounding conductors that connect to the receptacles should connect to protective earth at the service equipment.

Electrical Power for DC Units

Only a -48 VDC supply that complies with the Safety Extra Low Voltage (SELV) requirements of EN 60950 can connect to the IGX DC input.

For DC supply connections, consult local and/or national codes for proper conductor sizing. The conductors must be suitable for 20 Amps. Wiring that is 10 to 12 AWG (4 sq. mm) is adequate.

Bonding and Grounding

To maintain the full EMI and EMC integrity of this equipment, it must be bonded to an Integrated Ground Plane or an Isolated Ground Plane network. The purpose of this is to mitigate the damaging effects to equipment from Electrostatic Discharge and Lightning. Refer to the latest edition of ITU Recommendation K.27 or Bellcore GR-1089-CORE requirements to ensure that the correct Bonding and Grounding procedures are followed. As recommended in these documents, a frame bonding connection is provided on the StrataCom STRATM cabinet for rack-mounted systems and on the stand-alone cabinets.

Refer to "Making the Frame Bonding (Ground) Connection " later in this chapter for information on the locations of the frame bonding connections and how to make a connection.

Except for the AC power supply module, every module in a rack-mount system relies on the rack itself for grounding. Therefore, the rack must be properly connected to protective earth before operating the system.

A DC-powered IGX must have grounding conductors that connect at two separate locations, as follows:

CEPT Requirements

These requirements may be relevant to a private network connected to the public switched networks in some international service areas.


Note Cables must be attached so that their removal requires a tool.

STRATM Seismic Anchoring

This section describes installing the STRATM cabinet with the optional stability plate for seismic anchoring. If the stability plate is not present, go to the next section. To set up the STRATM cabinet with the stability plate:


Step 1   Use the dimensions in Figure 2-3 to drill the holes for installing the stability plate.

Step 2   Remove the stability plate from the base of the STRATM cabinet. Save these nuts and bolts.

Step 3   With the user-provided anchoring bolts, attach the stability plate to the floor.

Step 4   Roll the STRATM cabinet over the stability plate as Figure 2-4 illustrates.

Step 5   Using the nuts and bolts from the shipping setup, secure the STRATM cabinet to the stability plate.


Figure 2-1: Stability Plate Dimensions

Figure 2-2:
STRATM Installation Over Stability Plate

IGX 8 Installation

Installing an IGX 8 requires the following tools and equipment:

Stand-Alone System Installation

The installation steps consist of placing the stand-alone IGX 8 at its operating location, unpacking it, and verifying the integrity of the enclosure and power connections. Note that the cabinet is 19.9" wide.

After the system is at its operational location, follow the steps for connecting power. If the system has an AC power source, go to "AC Power Connections" section. If the system has a DC power source, go to the "DC Power Connections" section.

Rack-Mount Installation

The rack-mount IGX 8 fits in a 19 inch (48.25 cm.) rack with a minimum of 17.75 inches between rails. For mounting the chassis in a rack, brackets are attached to the front of the chassis. A pair of mounting brackets are attached at the back of the chassis after it is placed in the rack. Brackets for a mid-rack mounting also come with the kit.

Because of the weight of the IGX 8, StrataCom includes two temporary spacer brackets and a temporary mounting bracket to help with the installation. These pieces are removed after installation. The temporary spacer brackets stabilizes the rack, and the temporary mounting bracket together with the spacer brackets creates a partial shelf onto which the installers can slide the node. These pieces support the system while installers secure the permanent front and back mounting brackets to the rack.

Caution If an IGX is mounted in a cabinet, be sure an unrestricted air flow is available in and out of the enclosure.

To install the IGX in a rack:


Step 1   Decide the IGX 8 position in the rack. See Figure 2-3 for external dimensions. Note that the vertical spacing between the IGX 8 and other components, such as a BPX or AXIS shelf, must be in the range .047" to .077" (0.119 cm to 0.196 cm).


Figure 2-3: IGX 8 Rack Mounting Dimensions
Caution If moving a STRATM cabinet is necessary for installing the IGX 8, do not push the cabinet at its sides. Instead, grip the cabinet at the front or back edges to maneuver it to the setup location.

Step 2   At the front of the rack, attach the temporary spacer bracket and temporary mounting brackets so that the uppermost portion of these pieces are at the bottom of the intended location of the IGX 8. Figure 2-4 shows a temporary spacer and mounting bracket in a STRATM cabinet.


Figure 2-4: Temporary Spacer Bracket and Mounting Bracket

Step 3   Position the IGX 8 in front of the cabinet. This position should be such that the back of the IGX card cage faces the front of the rack. If not already done, remove the foam strips from the sides, front, and back.

Step 4   Remove the attached mounting brackets (filler plates) for the stand-alone version. The mounting brackets for the rack-mount go in these places. See Figure 2-5 for the locations of the mounting brackets.

Step 5   Attach the front mounting brackets to the IGX 8.

Caution An IGX 8 requires a 2 or 3-person lift to put it in the rack.

Step 6   This step requires one person on each side of the IGX card cage. Lift and slide the card cage into the rack at the front of the rack. Slide the IGX 8 to the back and rest the rear of the system on the temporary mounting brackets and spacer.

Step 7   Secure the front bracket (or mid-mount bracket) to the rack. The mid-mount brackets require the threaded rolling screws which the IGX 8 kit includes. Attach the IGX 8 to the rack with eight #10-32 machine screws.


Figure 2-5: Rack-Mount Cabinet
Caution Make sure that mounting the equipment does not create a hazardous condition due to uneven mechanical loading. The equipment rack should be securely supported.

Step 8   Attach the permanent rear mounting brackets to the rack.

Step 9   Remove the temporary mounting brackets and temporary spacer bracket.

Step 10   If this is a DC-powered system, go to "DC Power Connections" section.

Step 11   Go to the procedures in the chapter titled "Card Installation and Node Startup."

IGX 16/32 System Installation

Installing an IGX requires the following tools and equipment:

Rack-mount systems come with the parts described in the assembly instructions.

Stand-Alone System Installation

StrataCom stand-alone systems come with all components installed in the cabinet. So, the installation steps consist of placing the unit at its operational location, unpacking it, and verifying the structural and power connection integrity before turning on the power. Note that a stand-alone cabinet is 19.9" wide. The adjustable levelers require a 5/8" wrench. If the system has an AC power source, go to the "AC Power Connections"section. If the system has a DC power source, go to the "DC Power Connections" section.

IGX 16 Rack Mount Installation

The rack-mount IGX 16 fits in a 19 inch (48.25 cm.) rack. The front of each assembly has flanges that serve as the front mounting brackets. The assembly kit contains other brackets for different mounting setups. The following order of component installation is the most convenient and efficient. For some of these components, separation sections follow that contain detailed installation steps.

    1. Optional AC power assembly

    2. Cooling unit

    3. Card cage

    4. Exhaust plenum

Note that the vertical spacing between components, such as the card cage and fan tray, must be in the range .047" to .077" (0.119 cm to 0.196 cm).

The miscellaneous parts kit for rack systems contains brackets for both a STRATM cabinet and a user-supplied rack. The kit includes mid-mount brackets for open racks.

The rear-mount brackets attach to the rear vertical rail in a STRATM cabinet. Each of these brackets has a horizontal flange upon which the back of each IGX component rests. The front of each assembly chassis has flanges that serve as the front mounting brackets.

Caution If an IGX is mounted in a user-supplied cabinet, be sure an unrestricted air flow is available in and out of the enclosure. If necessary, contact the ISC for assistance.

To install the IGX in a rack:


Step 1   Decide on the IGX location. See Figure 2-6 for dimensions (Figure 2-7 for metric).

Caution When moving a STRATM cabinet, do not push the cabinet at its sides. Instead, grip its front or back edges.

Step 2   To install the optional AC power supply kit, do the steps in the "Installing the AC Power Supply Assembly" section later in this chapter.

Step 3   To install the cooling unit, do the steps in the "Installing the Cooling Unit" section later in this chapter.

Step 4   Position the IGX card cage so that the back of it faces the rack.

Caution An empty IGX card cage weighs 75 pounds (34 Kgs.) and requires a 2 or 3-person lift to move into place.

Figure 2-6: IGX 16 Rack Mounting Dimensions

Step 5   With one person on each side of the card cage, lift and slide it into the rack.

Step 6   Attach the cabinet to the rack with 8 #10-32 machine screws (from the kit).

Step 7   If the system is DC-powered, see the "DC Power Connections"section. For AC-powered systems, see the section titled "Installing the AC Power Supply Assembly." It appears later in this chapter.

Caution Make sure that mounting the equipment does not create a hazardous condition due to uneven mechanical loading. The equipment rack should be securely supported.

IGX 32 Rack Mount Installation

The IGX 32 is designed for mounting in a 19 inch (48.25 cm.) equipment rack. The following order of component installation is the most convenient and efficient. For some of these components, separation sections are named that contain detailed installation steps.

    1. Optional AC power assembly

    2. Lower cooling unit

    3. Lower card cage

    4. Upper card cage

    5. Ribbon cables for connecting upper and lower backplanes

    6. Card cage tunnel around backplane ribbon cables

    7. Upper cooling unit (also called booster fan unit)

    8. Exhaust plenum

The miscellaneous parts kit contains brackets for rack-mounting in either a STRATM cabinet or a user-supplied rack. The kit includes mid-mount brackets for open racks. For a STRATM cabinet, the rear-mount brackets attach to the rear vertical rail. Each of these brackets has a horizontal flange upon which the back of an individual component rests. The front of each assembly chassis has flanges that serve as front mounting brackets.

Caution If an IGX goes in a user-supplied cabinet, be sure air can freely flow in and out of the enclosure. Note also that the vertical spacing between components, such as the card cage and fan tray, must be in the range .047" to .077" (0.119 cm to 0.196 cm).
Caution When moving a STRATM cabinet, do not push the cabinet at its sides. Instead, grip the front or back edges.

Step 1   Refer to Figure 2-7 for component dimensions. Note that, although Figure 2-7 shows mid-mount and rear-mount brackets, these brackets are not normally used together.

Step 2   To install the optional AC power supply kit, do the steps in the "Installing the AC Power Supply Assembly" section next.

Step 3   To install the cooling unit, do the steps in the section titled "Installing the Cooling Unit" later in this chapter.

Step 4   Install the brackets for the card cages.

Step 5   Position the IGX card cage so the back of it faces the front of the cabinet.


Figure 2-7: IGX 32 Rack Mounting Dimensions
Caution An empty card cage requires a 2 or 3-person lift to move.

Step 6   With one person on each side of the card cage, lift it into the rack. In a STRATM cabinet, rest the back of the card cage on the rear-bracket flange.

When mid-mount brackets are used, screw the card cage to the brackets with #10-32 machine screws from the miscellaneous parts kit.

Step 7   Secure the front of the card cage to the front of the rack with #10-32 machine screws from the miscellaneous parts kit.

Warning Make sure that mounting the equipment does not create a hazardous condition due to uneven mechanical loading. The equipment rack should be securely supported.

Step 8   The folded ribbon cables that connect the upper and lower backplanes pass through a cut-out space in the card cages. The cables connect to two, 100-pin connectors on the front of each backplane. See Figure 2-8. If NPM cards are present, these and possibly other front cards need removing prior to ribbon cable installation.

Connect the cable from the upper connector of the upper backplane to the upper connector in the lower backplane.

Connect the cable from the lower connector of the upper backplane to the lower connector in the lower backplane.

Step 9   A two-piece conduit called the card cage tunnel surrounds the ribbon cables and sits in the cut-out space of the card cages. Fit the pieces of the card cage tunnel around the ribbon cables and screw this unified piece into the cut-out space. Figure 2-8 shows the card cage tunnel in its normal location and prior to assembly.

Step 10   Slip the ribbon cables through the fastener clamps, then attach the fastener clamps (which include a self-adhesive base) to the side of the card cage. See Figure 2-8.

Step 11   If this is an AC-powered system, do the procedures in the section titled "Installing the AC Power Supply Assembly." It appears later in this chapter.

Step 12   If this is a DC-powered system, go to the section titled "DC Power Connections" It appears later in this chapter.


Figure 2-8: IGX 32 Backplane Connector Cables

Installing the AC Power Supply Assembly

If the IGX 16 or 32 uses an AC power source, proceed with this section. In a rack-mount system, the AC Power Supply Assembly is shipped separately (as are all the other assemblies). The first assembly to install in a rack-mount system is the AC power supply assembly.

The AC power supply assembly consists of the following items:

Power supply installation or replacement requires the following tools:

Understanding the AC Power Supply Configuration

The setup for power supplies depends on the number of AC power inputs, the IGX model, and the number of cards in the system. The minimum configuration is one AC source and one supply. This minimum number applies to the IGX 16: with 12 or fewer cards, 1 supply is enough. Figure 2-9 illustrates the alphanumeric slot designations in a full tray. The paragraphs that follow refer to these designations.


Figure 2-9: Power Supply Slot Designations

Redundancy

Two types of redundancy exist in the AC power supply configuration. One redundancy is that of AC power inputs. A redundant AC power source from a building circuit that is separate from the other AC circuit provides backup if one AC circuit at the site fails. The other redundancy is that of the 875-Watt power supply modules. Redundancy of the 875-Watt supplies provides a backup if a supply fails.

In supporting the two types of redundancy, power supply arrangements differ, as follows:

Power Supply Quantities

Table 2-1 shows the required number of power supplies for the different IGX systems. In Table 2-1 , the locations for primary (or minimal) power supplies are marked with an X. The primary supplies reflect redundancy of AC inputs and backup supplies. An O indicates a slot that must have a supply because the card cage contains more than 12 cards.

In Table 2-1 , the System column lists the IGX model number coupled with the number of AC inputs and whether the single-AC input models have power supply redundancy. The table also shows the slot locations A through F and the part number of the kit that contains all the pieces for the item in the System column. Extra supplies for more than 12 cards (O) are not a part of a kit under Kit Part No. but have another part number. The part number of a supply ordered to fill extra power demands is IGX-AC-PS.


Table 2-1: Locations of Primary and Additional Supplies
System A B C D E F Kit Part No.

IGX 16: 1 AC input, no power supply redundancy

X

O

IGX16-AC1-1

IGX 16: 1 AC input, with power supply redundancy

X

X

O

IGX16-AC2-1

IGX 16: 2 AC inputs

X

O

X

O

IGX16-AC2-2

IGX 32:1 AC input, no power supply redundancy

X

X

O

IGX32-AC2-1

IGX 32: 1 AC input, with power supply redundancy

X

X

X

O

IGX32-AC4-1

IGX 32: 2 AC inputs

X

X

O

X

X

O

IGX32-AC4-2

Note that, with all power supply configurations, locations for the power supplies begin at the lowest lettered slot on either side, and the occupied positions are contiguous. For example, in a dual AC system, insert a supply in A, B, D, and E.

AC Installation in a Rack-Mount Cabinet

The procedures in this section apply to both the IGX 16 and the IGX 32 in a rack. (For stand-alone systems, the power supplies are already installed.) To replace a power supply, follow the steps in the chapter titled "Repair and Replacement."


Step 1   Attach the mounting brackets to the frame. For illustrative purposes, Figure 2-10 shows mounting brackets at mid-frame and the back (using rear and mid-mount brackets is not a likely configuration). In this view of the cabinet, the rear bracket shown is labeled with a -00. Brackets on the other side of the system a -01.


Figure 2-10: Front of Rack Mount System

Step 2   This step may require more than one person. If rear-mount brackets are used, slide in the power supply tray so its back rests on the rear bracket.

For a mid-mount rack only, attach the tray to the mounting brackets with the head of each mounting screw on the inside of the tray and each associated nut on the outside of the bracket.

Step 3   Secure the front of the power supply tray with the front screws. When tightening each of the front screws, hold the adjacent front flange of the tray slightly to the outside so the hinged door can freely open and close. See "Front Flange" in Figure 2-10. The space between the right-angle edge of the flange and the edge of the hinged door should be approximately the width of a thumbnail.

Step 4   Install the power supplies. See Figure 2-11 for an illustration of a power supply. When a power supply almost reaches the end of the slot in the tray, a slight resistance is encountered. Push the power supply slightly farther in to achieve the final position and full connector mating.

Step 5   At the front of each supply, secure the supply to the tray by tightening the captive screw at the bottom/front of the supply.


Figure 2-11: Power Supply (viewed from front and left)

Step 6   For slots without a power supply, the hinged door has a removable, dummy panel.

Step 7   Close the hinged door and secure it with the screw at the top-center of the door. For the next step, refer to Figure 2-12, Figure 2-13, and Figure 2-14.

Step 8   Connect the power cables according to the applicable AC configuration shown in Figure 2-12. The cables in Figure 2-12 differ only in length: pinouts are identical. Attach cable 215982-01 from the far right connector—labeled A 1-16 in Figure 2-13—to the lower connector on the upper PE-BC. Figure 2-14 shows where system power connects to the PE-BC. It also shows the blank plate over an unused connection. If power supply trays D-F contain one or more supplies, run cable 215982-02 from the connector on the far left (B 1-16) to the upper connector on the PE-BC. See Figure 2-12 and Figure 2-13. For an IGX 32, run cable 215982-00 from the connector labeled 17-32 to the lower connector on the lower PE-BC.

Step 9   Attach the cable guard and tighten the captive screw at its base.

Step 10   Go to the "Installing the Cooling Unit" section.


Figure 2-12: Wire Diagrams for Different Power Configurations

Figure 2-13:
AC Power Supply Shelf Back View

Figure 2-14:
Inserting System Power Connector to E-Card, AC-Powered System

Installing the Cooling Unit

This section describes how to install the main fan tray (Fan Tray 1) in an IGX 16 and 32 and the upper or booster fan tray (Fan Tray 2) in an IGX 32. Figure 2-15 shows the main fan tray. Figure 2-16 shows the locations of Fan Tray 1 and Fan Tray 2 in an IGX 32.


Figure 2-15: Fan Tray Assembly

Two cables exist for supplying power to the fans. The short fan power cable is used in both the IGX 16 and the IGX 32. The long "Y" cable is used in the IGX 32 only. See Figure 2-16. In an IGX 16, the short cable connects to connector "Fan 1" of the PE-BC.

In an IGX 32, the short cable goes from the "Fan 2" connector of the upper PE-BC to the power connectors on Fan Tray 2. One branch of the Y cable for Fan Tray 1 is significantly longer than the other branch. The longer branch connects to the "Fan 1" connector of the upper PE-BC. The shorter branch connects to the "Fan 1" connector of the lower PE-BC.

To install the cooling unit assembly:


Step 1   Examine the front and back of the fan tray to be familiar with the setup. Note that, for the bottom fan tray, the captive screws that secure the fan tray are in the front. For the booster fan tray, the captive screws reside at the back of the cabinet.

Step 2   Slide in the cooling unit. and secure it by tightening the four rack screws.

Step 3   On the PE-BCs, plug each D-connector of the appropriate fan power cable into the appropriate PE-BC connector.

Step 4   Plug the power connectors into the fan trays. At the power receptacles on each fan tray, the power connector is a latched housing. Plug P1 into connector P1. Plug P2 into connector P2. Refer to Figure 2-15.

Step 5   Attach the clamp for the fan power cord to the chassis.

Step 6   For lower fan tray installation, attach the air intake bezel.

Step 7   When power is turned on, make sure all fans are running, and execute dsppwr.


Figure 2-16: IGX 32 Back View

Making Power and Ground Connections

This section contains information on making connections to AC and DC-powered systems.

Warning Before connecting power, make sure all IGX circuit breakers are off.

Making the Frame Bonding (Ground) Connection

The STRATM cabinet designed by StrataCom comes with attached studs (with hardware for securing a ground conductor to the studs) at the top and bottom of the cabinet for securing the grounding conductors. These studs a 1/4" by 20 threads per inch. Figure 2-17 shows the STRATM cabinet with the ground attachment studs in the upper and lower parts of the cabinet.

A stand-alone cabinet has provisions for mounting grounding conductors on the chassis by screws. In the stand-alone cabinet, this provision is a pair of captive nuts (threaded holes) for the screws on the mounting rail of the chassis (1/4" by 20 threads per inch). Figure 2-17 shows the location of the captive nuts and screws in a stand-alone cabinet for securing in the ground attachments.

The attachment points in the STRATM and stand-alone cabinets are indicated by a ground symbol on the cabinet near the point of attachment.

STRATM Cabinet Connections

StrataCom recommends the following stacking order for attaching a ground conductor to the frame of a STRATM cabinet:


Step 1   Place an external, "toothed starwasher" onto the stud.

Step 2   Place the connector terminating the grounding conductor closed-loop ring or two-hole compression fitting onto the stud.

Step 3   Place another external, "toothed starwasher or lockwasher" onto the stud.

Step 4   Screw a nut onto the threaded stud.

Stand-Alone Cabinet Connections

StrataCom recommends the following stacking order for attaching a ground conductor to the frame of a standalone enclosure:


Step 1   Place an external, "tooth starwasher" onto the screw.

Step 2   Place the connector terminating the grounding conductor closed-loop ring or two-hole compression fitting.

Step 3   Place another external, "tooth starwasher or lockwasher."

Step 4   Screw the entire assembly into the captive nut in the mounting rail beneath the cover plate. See Figure 2-18 for an illustration of this stacking order in an IGX 16. Figure 2-19 shows the location of the frame bonding connection on an IGX 8.


Figure 2-17: Frame Bonding Connection in STRATM Cabinet

Figure 2-18:
Frame Bonding Connections in IGX 16 Stand-Alone

Figure 2-19: IGX 8
Frame Bonding Connections

AC Power Connections

StrataCom provides at least one, eight-foot (three meter) power cord with each AC Power Supply Assembly. To make AC power connections to the IGX:


Step 1   Make sure all AC and system power circuit breakers are in the OFF position.

Step 2   Make sure the AC plug wiring has the correct relationship. Figure 2-20 shows the voltage across the wires in an IGX 8 plug. Figure 2-22 shows the voltage across the wires in an IGX 16/32 plug.


Figure 2-20: IGX 8 AC Connection Wiring

Step 3   Plug the power cord into the IEC connector and tighten the screw on the clamping ring. See Figure 2-21 for an example of an IGX 8 and Figure 2-23 for an IGX 16.


Figure 2-21: IGX 8 Circuit Breakers

Figure 2-22:
IGX 16/32 AC Connection Wiring

Figure 2-23:
IGX 16 Circuit Breakers

Step 4   Plug the AC power cord into a single-phase wall outlet rated for a nominal voltage.

For an IGX 8, the AC voltage should be between 200 to 240 VAC or 100 to 120 VAC. The outlet must also be capable of supplying up to 12 Amps (13 Amps in the UK). The building circuit should be protected with a 15 or 20 Amp circuit breaker.

For an IGX 16 or 32, the AC voltage should be between 200 and 240 VAC. Each outlet must also be capable of supplying up to 16 Amps (13 Amps in the UK, where the plug has a built-in, 13 Amp fuse). In North America, the building circuit should be protected with a 20 Amp circuit breaker.

Step 5   For the dual power feed version, plug each power cord into a receptacle that connects to a separate building circuit to provide backup if one building circuit fails. Each building circuit should have a 15 or 20 Amp circuit breaker.

Step 6   The ground (green) wire of the AC power cord is connected to the IGX for safety ground. Make sure each AC receptacle in the building is grounded.

Step 7   In addition to the preceding, StrataCom recommends that you provide an AC power strip with at least four outlets. Place the strip near the IGX to supply optional modems, CSUs, DSUs, or test equipment. Be sure to connect this power strip to an AC source voltage that is standard for the region (for example, 115 VAC in North America or 230 VAC in Europe).


Note Neither the
AC power supplies nor any other components have test points for checking power supply voltages. For a visual check when power is on, observe whether the AC OK LED and DC OK LED are lit. Also, use the dsppwr command to check the state of power supplies.

DC Power Connections

A system that uses a DC power source have one or two configurations, as follows:

Wiring is connected from one or two -48 VDC power sources to one or two DC PEMs per shelf. StrataCom does not provide the wire between the node and the source. Instead, the installer or customer must supply it. These wires should be capable of carrying 20 Amps. The diagrams on the pages that follow show DC wiring for single and redundant DC sources for all IGX models.


Figure 2-24: Single Shelf With Single DC Source

Figure 2-25:
Single Shelf With Dual DC Sources

Figure 2-26:
IGX 32 With a Single DC Source

Figure 2-27:
IGX 32 With Redundant DC Sources

As the detailed steps on the following pages explain, installing DC power consists of attaching the three wires of the DC power source to a removable wiring block, then plugging that block into the connector on the PEM. The PEM is plugged into the PE-BC. Figure 2-28 is a view of a PE-BC (out of the card cage) with the PEM wired up and plugged into the PE-BC. Figure 2-28 shows a non-redundant DC power configuration. Note the blank plate that covers the unused connection.


Note A DC-powered system makes no distinction between a primary and redundant PEM (unlike the redundancy scheme in an AC-powered system). However, StrataCom suggests putting a label of some type on the PEM to identify the branch circuit to which it goes.

Figure 2-28: PE-BC and DC PEM With Plug
Warning Remember that this is a positive ground system. Ensure that polarity of the DC input wiring is correct. Under certain conditions, connections with reversed polarity may trip the primary circuit breaker and/or damage the equipment.

Make sure the circuit breaker is in the OFF position.

To make a DC power connection:


Step 1   For both stand-alone systems, the cable guard (located at the right edge of the chassis) remains off until the system is ready to power up. Remove the cable guard by loosening the captive screw at its base then swinging it away from the chassis (do this latter movement holding the top of the cable guard in place while moving the bottom of it away from the chassis).

Step 2   Insert and secure the stripped ends of the wire in the wiring block according to the scheme in Figure 2-29 and Figure 2-30 . Figure 2-30 illustrates the polarity of each connection on the pluggable terminal block. The numbers start with 1 at the bottom and go to 3. The connection at the bottom is for the -48 VDC wire. The middle wire is Safety Ground. The connection at the top is for the positive return wire (for the -48 VDC). Figure 2-30 shows the assembly with an example wire and the screw that secures it in the pluggable wire block.


Figure 2-29: Polarities at Pluggable Terminal Block

Step 3   Attach the pluggable terminal block to the receptacle on the PEM.

Step 4   Loop the DC wiring through the strain relief clamp.


Figure 2-30:
Pluggable Terminal Block
Warning For personnel safety, the green or green/yellow wire must connect to safety (earth) ground at both the equipment and at the supply side of the DC wiring.

Step 5   Connect the DC input wiring to a DC source capable of supplying at least 20 Amps (typical). The -48 VDC power source in the building should have a 25 A DC circuit breaker. The building's wiring should include an easily accessible disconnect device. Make sure the ground wire connects to a reliable building (earth) ground.

Step 6   Leave the cable guard off until power is on.

Step 7   Before you turn on the system power, check the supply voltage. Use the screws at positions 1 and 3 on the pluggable terminal block as a convenient measuring point. Also, check the impedance between the safety ground (screw at location 2 on the pluggable terminal block) and the chassis. It should be close to 0.

Step 8   Turn on the power, and check the voltage at the screws at positions 1 and 3 on the pluggable terminal block.

Step 9   Turn off the power, and go to the chapter titled "Card Installation and Node Startup."


Note The building circuit breaker provides primary over-current protection. In North America, this protection should accord with standards NEC ANSI/NFPA70 in the U.S or CEC C22.1 in Canada for excess current, short circuits, and earth faults.