Alarm Management Reference

21.1  Overview

21.2  Alarm Counts on the LCD for a Node, Slot, or Port

21.3  Alarm Display

21.3.1  Viewing Alarms by Time Zone

21.3.2  Controlling Alarm Display

21.3.3  Filtering Alarms

21.3.4  Conditions Tab

21.3.5  Controlling the Conditions Display

21.3.6  Viewing History

21.4  Alarm Severities

21.5  Alarm Profiles

21.5.1  Creating and Modifying Alarm Profiles

21.5.2  Alarm Profile Buttons

21.5.3  Alarm Profile Editing

21.5.4  Alarm Severity Options

21.5.5  Row Display Options

21.5.6  Applying Alarm Profiles

21.6  Alarm Suppression

21.7  External Alarms and Controls

21.7.1  External Alarms

21.7.2  External Controls

21.7.3  Virtual Wires


Alarm Management Reference


This chapter describes Cisco Transport Controller (CTC) alarm management. To troubleshoot specific alarms, refer to the Cisco ONS 15454 Troubleshooting Guide (for ANSI shelves) or the Cisco ONS 15454 SDH Troubleshooting Guide (for ETSI shelves).


Note Unless otherwise specified, "ONS 15454" refers to both ANSI and ETSI shelf assemblies.


Chapter topics include:

Overview

Alarm Counts on the LCD for a Node, Slot, or Port

Alarm Display

Alarm Severities

Alarm Profiles

Alarm Suppression

External Alarms and Controls

21.1  Overview

CTC detects and reports alarms generated by the Cisco ONS 15454 and the larger network. You can use CTC to monitor and manage alarms at the card, node, or network level. Default alarm severities conform to the Telcordia GR-253-CORE standard, but you can set alarm severities in customized alarm profiles or suppress CTC alarm reporting. For a detailed description of the standard Telcordia categories employed by Optical Networking System (ONS) nodes, refer to the Cisco ONS 15454 Troubleshooting Guide or the Cisco ONS 15454 SDH Troubleshooting Guide.


Note ONS 15454 alarms can also be monitored and managed through Transaction Language One (TL1) or a network management system (NMS).


21.2  Alarm Counts on the LCD for a Node, Slot, or Port

You can view node, slot, or port-level alarm counts and summaries using the buttons on the ONS 15454 LCD panel. The Slot and Port buttons toggle between display types; the Slot button toggles between node display and slot display, and the Port button toggles between slot and port views. Pressing the Status button after you choose the display mode changes the display from alarm count to alarm summary.

The ONS 15454 has a one-button update for some commonly viewed alarm counts. If you press the Slot button once and then wait eight seconds, the display automatically changes from a slot alarm count to a slot alarm summary. If you press the Port button to toggle to port-level display, you can use the Port button to toggle to a specific slot and to view each port's port-level alarm count. Figure 21-1 shows the LCD panel layout.

Figure 21-1 Shelf LCD Panel

21.3  Alarm Display

In the card, node, or network CTC view, click the Alarms tab to display the alarms for that card, node, or network. The Alarms window shows alarms in compliance with Telcordia GR-253-CORE. This means that if a network problem causes two alarms, such as loss of frame (LOF) and loss of signal (LOS), CTC only shows the LOS alarm in this window because it supersedes the LOF and replaces it.

The Path Width column in the Alarms and Conditions tabs expands on the alarmed object information contained in the access identifier (AID) string (such as "STS-4-1-3") by giving the number of STSs contained in the alarmed path. For example, the Path Width tells you whether a critical alarm applies to an STS1 or an STS48c. The column reports the width as a 1, 3, 6, 12, 48, etc. as appropriate, understood to be "STS-N."

Table 8-1 on page 8-6 lists the column headings and the information recorded in each column and Table 8-2 on page 8-7 provides the color codes for alarm and condition severities.

For a list of circuits with raised alarms, see the "NTP-G66 View Alarm-Affected Circuits" procedure on page 8-14.

21.3.1  Viewing Alarms by Time Zone

By default, alarms and conditions are displayed with the time stamp of the CTC workstation where you are viewing them. However, you can set the node to report alarms (and conditions) using the time zone where the node is located. See the "DLP-G118 Display Alarms and Conditions Using Time Zone" task on page 8-10 for instructions.

21.3.2  Controlling Alarm Display

You can control the display of the alarms shown on the Alarms window. Table 21-1 shows the actions you can perform in the Alarms window.

Table 21-1 Alarm Display 

Button/Check Box/Tool
Action

Filter button

Allows you to change the display on the Alarms window to show only alarms that meet a certain severity level, occur in a specified time frame, or reflect specific conditions. For example, you can set the filter so that only critical alarms display in the window.

If you enable the Filter feature by clicking the Filter button in one CTC view, such as node view, it is enabled in the others as well (card view and network view).

Synchronize button

Updates the alarm display. Although CTC displays alarms in real time, the Synchronize button allows you to verify the alarm display. This is particularly useful during provisioning or troubleshooting.

Delete Cleared Alarms button

Deletes alarms that have been cleared.

AutoDelete Cleared Alarms check box

If checked, CTC automatically deletes cleared alarms.

Filter tool

Enables or disables alarm filtering in the card, node, or network view. When enabled or disabled, this state applies to other views for that node and for all other nodes in the network. For example, if the Filter tool is enabled in the node (default login) view Alarms window, the network view Alarms window and card view Alarms window also show the tool enabled. All other nodes in the network also show the tool enabled.


21.3.3  Filtering Alarms

The alarm display can be filtered to prevent the display of alarms with certain severities or alarms that occurred between certain dates. You can set the filtering parameters by clicking the Filter button at the bottom-left of the Alarms window. You can turn the filter on or off by clicking the Filter tool at the bottom-right of the window. CTC retains your filter activation setting. For example, if you turn the filter on and then log out, CTC keeps the filter active the next time you log in.

See the "NTP-G69 Enable, Modify, or Disable Alarm Severity Filtering" procedure on page 8-24.

21.3.4  Conditions Tab

The Conditions window displays retrieved fault conditions. A condition is a fault or status detected by ONS 15454 hardware or software. When a condition occurs and continues for a minimum period, CTC raises a condition, which is a flag showing that this particular condition currently exists on the ONS 15454. See the "DLP-G120 View Conditions" task on page 8-11.

The Conditions window shows all conditions that occur, including those that are superseded. For instance, if a network problem causes two alarms, such as LOF and LOS, CTC shows both the LOF and LOS conditions in this window (even though LOS supersedes LOF). Having all conditions visible can be helpful when troubleshooting the ONS 15454. If you want to retrieve conditions that obey a root-cause hierarchy (that is, LOS supersedes and replaces LOF), you can exclude the same root causes by checking a check box in the window.

Fault conditions include reported alarms and Not Reported or Not Alarmed conditions. Refer to the trouble notifications information in the Cisco ONS 15454 Troubleshooting Guide or Cisco ONS 15454 SDH Troubleshooting Guide for more information about alarm and condition classifications.

21.3.5  Controlling the Conditions Display

You can control the display of the conditions on the Conditions window. Table 21-2 shows the actions you can perform in the window.

Table 21-2 Conditions Display 

Button
Action

Retrieve

Retrieves the current set of all existing fault conditions, as maintained by the alarm manager, from the ONS 15454.

Filter

Allows you to change the Conditions window display to only show the conditions that meet a certain severity level or occur in a specified time frame. For example, you can set the filter so that only critical conditions display on the window.

There is a Filter button on the lower-right of the window that allows you to enable or disable the filter feature.

Exclude Same Root Cause

Retrieves conditions that obey a root-cause hierarchy (LOS supersedes and replaces LOF).


21.3.5.1  Retrieving and Displaying Conditions

The current set of all existing conditions maintained by the alarm manager can be seen when you click the Retrieve button. The set of conditions retrieved is relative to the CTC view. For example, if you click the button while displaying the node view, node-specific conditions appear. If you click the button while displaying the network view, all conditions for the network (including ONS 15454 nodes and other connected nodes) appear, and the card view shows only card-specific conditions.

You can also set a node to display conditions using the time zone where the node is located, rather than the time zone of the PC where they are being viewed. See the "DLP-G118 Display Alarms and Conditions Using Time Zone" task on page 8-10 for instructions.

21.3.5.2  Conditions Column Descriptions

Table 21-3 lists the Conditions window column headings and the information recorded in each column.

Table 21-3 Conditions Column Description 

Column
Information Recorded

Date

Date and time of the condition.

Object

TL1 AID for the condition object. For an STSmon or VTmon, the object.

Eqpt Type

Card type in this slot.

Slot

Slot where the condition occurred (appears only in network and node view).

Port

Port where the condition occurred. For STSTerm and VTTerm, the port refers to the upstream card it is partnered with.

Path Width

Width of the data path.

Sev1

Severity level: CR (Critical), MJ (Major), MN (Minor), NA (Not Alarmed), NR (Not Reported).

SA 1

Indicates a service-affecting alarm (when checked).

Cond

The error message/alarm name; these names are alphabetically defined in the Cisco ONS 15454 Troubleshooting Guide or Cisco ONS 15454 SDH Troubleshooting Guide.

Description

Description of the condition.

1 All alarms, their severities, and service-affecting statuses are also displayed in the Condition tab unless you choose to filter the alarm from the display using the Filter button.


21.3.5.3  Filtering Conditions

The condition display can be filtered to prevent display of conditions (including alarms) with certain severities or that occurred between certain dates. You can set the filtering parameters by clicking the Filter button at the bottom-left of the Conditions window. You can turn the filter on or off by clicking the Filter tool at the bottom-right of the window. CTC retains your filter activation setting. For example, if you turn the filter on and then log out, CTC keeps the filter active the next time your user ID is activated.

21.3.6  Viewing History

The History window displays historic alarm or condition data for the node or for your login session. You can chose to display only alarm history, only events, or both by checking check boxes in the History > Node window. You can view network-level alarm and condition history, such as for circuits, at that level. At the node level, you can see all port (facility), card, STS, and system-level history entries. For example, protection-switching events or performance-monitoring threshold crossings appear here. If you double-click a card, you can view all port, card, and STS alarm or condition history that directly affects the card. See the "DLP-G116 View Alarm or Event History" task on page 8-8.

The ONS 15454 can store up to 640 critical alarm messages, 640 major alarm messages, 640 minor alarm messages, and 640 condition messages. When any of these limits is reached, the ONS 15454 discards the oldest events in that category.


Note In the Preference dialog General tab, the Maximum History Entries value only applies to the Session window.


Different views of CTC display different kinds of history:

The History > Session window is shown in network view, node view, and card view. It shows alarms and conditions that occurred during the current user CTC session.

The History > Node window is only shown in node view. It shows the alarms and conditions that occurred on the node since CTC software was operated on the node.

The History > Card window is only shown in card view. It shows the alarms and conditions that occurred on the card since CTC software was installed on the node.


Tip Double-click an alarm in the History window to display the corresponding view. For example, double-clicking a card alarm takes you to card view. In network view, double-clicking a node alarm takes you to node view.


If you check the History window Alarms check box, you display the node history of alarms. If you check the Events check box, you display the node history of Not Alarmed and transient events (conditions). If you check both check boxes, you retrieve node history for both.

21.3.6.1  History Column Descriptions

Table 21-4 lists the History window column headings and the information recorded in each column.

Table 21-4 History Column Description 

Column
Information Recorded

Num

Num (number) is the quantity of alarm messages received, and is incremented automatically as alarms occur to display the current total of received error messages. (The column is hidden by default; to view it, right-click a column and choose Show Column.)

Ref

Ref (reference) is a unique identification number assigned to each alarm to reference a specific alarm message that is displayed. (The column is hidden by default; to view it, right-click a column and choose Show Column.)

Date

Date and time of the condition.

Object

TL1 AID for the condition object. For an STSmon or VTmon, the object.

Slot

Slot where the condition occurred (only displays in network view and node view).

Port

Port where the condition occurred. For STSTerm and VTTerm, the port refers to the upstream card it is partnered with.

Path Width

Width of the data path.

Sev

Severity level: Critical (CR), Major (MJ), Minor (MN), Not Alarmed (NA), Not Reported (NR).

ST

Status: raised (R), cleared (C), or transient (T).

SA

Indicates a service-affecting alarm (when checked).

Cond

Condition name.

Description

Description of the condition.

Eqpt Type

Card type in this slot.


21.3.6.2  Retrieving and Displaying Alarm and Condition History

You can retrieve and view the history of alarms and conditions, including transient conditions (passing notifications of processes as they occur) in the CTC History window. The information in this window is specific to the view where it is shown (that is, network history in the network view, node history in the node view, and card history in the card view).

The node and card history views are each divided into two tabs. In node view, when you click the Retrieve button, you can see the history of alarms, conditions, and transients that have occurred on the node in the History > Node window, and the history of alarms, conditions, and transients that have occurred on the node during your login session in the History > Session window. In the card-view history window, after you retrieve the card history, you can see the history of alarms, conditions, and transients on the card in the History > Card window, or a history of alarms, conditions, and transients that have occurred during your login session in the History > Session window. You can also filter the severities and occurrence period in these history windows.

21.4  Alarm Severities

ONS 15454 alarm severities follow the Telcordia GR-253-CORE standard, so a condition might be Alarmed (at a severity of Critical [CR], Major [MJ], or Minor [MN]), Not Alarmed (NA), or Not Reported (NR). These severities are reported in the CTC software Alarms, Conditions, and History windows at all levels: network, shelf, and card.

ONS equipment provides a standard profile named Default listing all alarms and conditions with severity settings based on Telcordia GR-253-CORE and other standards, but users can create their own profiles with different settings for some or all conditions and apply these wherever desired. (See the "Alarm Profiles" section.) For example, in a custom alarm profile, the default severity of a carrier loss (CARLOSS) alarm on an Ethernet port could be changed from major to critical. The profile allows setting to Not Reported or Not Alarmed, as well as the three alarmed severities.

Critical and Major severities are only used for service-affecting alarms. If a condition is set as Critical or Major by profile, it will raise as Minor alarm in the following situations:

In a protection group, if the alarm is on a standby entity (the side not carrying traffic)

If the alarmed entity has no traffic provisioned on it, no service is lost

Because of this possibility of being raised at two different levels, the alarm profile pane shows Critical as CR / MN and Major as MJ / MN.

21.5  Alarm Profiles

The alarm profiles feature allows you to change default alarm severities by creating unique alarm profiles for individual ONS 15454 ports, cards, or nodes. A created alarm profile can be applied to any node on the network. Alarm profiles can be saved to a file and imported elsewhere in the network, but the profile must be stored locally on a node before it can be applied to the node, its cards, or its cards' ports.

CTC can store up to ten active alarm profiles at any time to apply to the node. Custom profiles can take eight of these active profile positions. Two other profiles, Default profile and Inherited profile, are reserved by the NE, and cannot be edited.The reserved Default profile contains Telcordia GR-253-CORE severities. The reserved Inherited profile allows port alarm severities to be governed by the card-level severities, or card alarm severities to be determined by the node-level severities.

If one or more alarm profiles have been stored as files from elsewhere in the network onto the local PC or server hard drive where CTC resides, you can utilize as many profiles as you can physically store by deleting and replacing them locally in CTC so that only eight are active at any given time.

See the "NTP-G68 Create, Download, and Assign Alarm Severity Profiles" procedure on page 8-16.

21.5.1  Creating and Modifying Alarm Profiles

Alarm profiles are created in the network view using the Provisioning > Alarm Profiles tabs. Figure 21-2 shows the default list of alarm severities. A default alarm severity following Telcordia GR-253-CORE standards is preprovisioned for every alarm. After loading the default profile or another profile on the node, you can clone a profile to create custom profiles. After the new profile is created, the Alarm Profiles window shows the original profile (frequently Default) and the new profile.

Figure 21-2 Network View Alarm Profiles Window


Note The alarm profile list contains a master list of alarms that is used for a mixed node network. Some of these alarms might not be used in all ONS nodes.



Note The Default alarm profile list contains alarm and condition severities that correspond when applicable to default values established in Telcordia GR-253-CORE.



Note All default or user-defined severity settings that are Critical (CR) or Major (MJ) are demoted to Minor (MN) in non-service-affecting situations as defined in Telcordia GR-474.



Tip To see the full list of profiles, including those available for loading or cloning, click the Available button. You must load a profile before you can clone it.



Note Up to 10 profiles, including the two reserved profiles (Inherited and Default) can be stored in CTC.


Wherever it is applied, the Default alarm profile sets severities to standard Telcordia GR-253-CORE settings. In the Inherited profile, alarms inherit, or copy, severity from the next-highest level. For example, a card with an Inherited alarm profile copies the severities used by the node housing the card. If you choose the Inherited profile from the network view, the severities at the lower levels (node and card) are copied from this selection.

You do not have to apply a single severity profile to the node-, card-, and port-level alarms. Different profiles can be applied at different levels. You could use the inherited or default profile on a node and on all cards and ports, but apply a custom profile that downgrades an alarm on one particular card. For example, you might choose to downgrade an OC-N unequipped path alarm (UNEQ-P) from Critical (CR) to Not Alarmed (NA) on an optical card because this alarm raises and then clears every time you create a circuit. UNEQ-P alarms for the card with the custom profile would not display on the Alarms tab (but they would still be recorded on the Conditions and History tabs.)

When you modify severities in an alarm profile:

All Critical (CR) or Major (MJ) default or user-defined severity settings are demoted to Minor (MN) in Non-Service-Affecting (NSA) situations as defined in Telcordia GR-474.

Default severities are used for all alarms and conditions until you create a new profile and apply it.

The Load and Store buttons are not available for Retrieve and Maintenance users.

The Delete and Store options will only display nodes to delete profiles from or store profiles to if the user has provisioning permission for those nodes. If the user does not have the proper permissions, CTC greys out the buttons and they are not available to the user.

21.5.2  Alarm Profile Buttons

The Alarm Profiles window displays six buttons at the bottom of the screen. Table 21-5 lists and describes each of the alarm profile buttons and their functions.

Table 21-5 Alarm Profile Buttons 

Button
Description

New

Creates a new profile.

Load

Loads a profile to a node or a file.

Store

Saves profiles on a node (or nodes) or in a file.

Delete

Deletes profiles from a node.

Compare

Displays differences between alarm profiles (for example, individual alarms that are not configured equivalently between profiles).

Available

Displays all profiles available on each node.

Usage

Displays all entities (nodes and alarm subjects) present in the network and which profiles contain the alarm. Can be printed.


21.5.3  Alarm Profile Editing

Table 21-6 lists and describes the five profile-editing options available when you right-click an alarm item in the profile column (such as Default).

Table 21-6 Alarm Profile Editing Options 

Button
Description

Store

Saves a profile in a node or in a file.

Rename

Changes a profile name.

Clone

Creates a profile that contains the same alarm severity settings as the profile being cloned.

Reset

Restores a profile to its previous state or to the original state (if it has not yet been applied).

Remove

Removes a profile from the table editor.


21.5.4  Alarm Severity Options

To change or assign alarm severity, left-click the alarm severity you want to change in the alarm profile column. Seven severity levels appear for the alarm:

Not Reported (NR)

Not Alarmed (NA)

Minor (MN)

Major (MJ)

Critical (CR)

Use Default

Inherited

Inherited and Use Default severity levels only appear in alarm profiles. They do not appear when you view alarms, history, or conditions.

21.5.5  Row Display Options

In the network or node view, the Alarm Profiles window (Alarm Profile Editor for Node view) displays three check boxes at the bottom of the window:

Only show service-affecting severities—If unchecked, the editor shows severities in the format sev1/sev2 where sev1 is a service-affecting severity and sev2 is not service-affecting. If checked, the editor only shows sev1 alarms.

Hide reference values—Highlights alarms with nondefault severities by clearing alarm cells with default severities.

Hide identical rows—Hides rows of alarms that contain the same severity for each profile.

21.5.6  Applying Alarm Profiles

In CTC node view, the Alarm Behavior window displays alarm profiles for the node. In card view, the Alarm Behavior window displays the alarm profiles for the selected card. Alarm profiles form a hierarchy. A node-level alarm profile applies to all cards in the node except cards that have their own profiles. A card-level alarm profile applies to all ports on the card except ports that have their own profiles.

At the node level, you can apply profile changes on a card-by-card basis or set a profile for the entire node. At the card-level view, you can apply profile changes on a port-by-port basis or set alarm profiles for all ports on that card. Figure 21-3 shows alarm profiles for an OPT-BST card.

Figure 21-3 OPT-BST Card Alarm Profiles

21.6  Alarm Suppression

ONS 15454 nodes have an alarm suppression option that clears raised alarm messages for the node, chassis, one or more slots (cards), or one or more ports. After they are cleared, these alarms change appearance from their normal severity color to white and they can be cleared from the display by clicking Synchronize. Alarm suppression itself raises an alarm called AS-CMD that is shown in applicable Alarms windows. Node-level suppression is shown in the node view Alarms window, and card or port-level suppression is shown in all views. The AS-CMD alarm itself is not cleared by the suppress command. Each instance of this alarm indicates its object separately in the Object column.

A suppression command applied at a higher level does not supersede a command applied at a lower level. For example, applying a node-level alarm suppression command makes all raised alarms for the node appear to be cleared, but it does not cancel out card-level or port-level suppression. Each of these conditions can exist independently and must be cleared independently.

Suppression causes the entity alarm to behave like a Not Reported event. This means that the alarms, having been suppressed from view in the Alarms window, are now only shown in the Conditions window. The suppressed alarms are displayed with their usual visual characteristics (service-affecting status and color-coding) in the window. The alarms still appear in the History window.

See the "NTP-G70 Suppress Alarms or Discontinue Alarm Suppression" procedure on page 8-28.


Note Use alarm suppression with caution. If multiple CTC or TL1 sessions are open, suppressing the alarms in one session suppresses the alarms in all other open sessions.


21.7  External Alarms and Controls

External alarm inputs can be provisioned on the Alarm Interface Controller-International (AIC-I) card for external sensors such as an open door and flood sensors, temperature sensors, and other environmental conditions. External control outputs on these two cards allow you to drive external visual or audible devices such as bells and lights. They can control other devices such as generators, heaters, and fans.

Up to 12 external alarm inputs and four external controls are available with the AIC-I card. If you also provision the alarm extension panel (AEP), there are 32 inputs and 16 outputs. The AEP is compatible with the ONS 15454 ANSI shelf only. It is not compatible with the ONS 15454 ETSI shelf.

See the "NTP-G72 Provision External Alarms and Controls on the Alarm Interface Controller-International Card" procedure on page 8-31.

21.7.1  External Alarms

You can provision each alarm input separately. Provisionable characteristics of external alarm inputs include:

Alarm Type—List of alarm types.

Severity—CR, MJ, MN, NA, and NR.

Virtual Wire—The virtual wire associated with the alarm.

Raised When—Open means that the normal condition is no current flowing through the contact, and the alarm is generated when current does flow; closed means that normal condition is to have current flowing through the contact, and the alarm is generated when current stops flowing.

Description—CTC alarm log description (up to 63 characters).


Note If you provision an external alarm to raise when a contact is open, and you have not attached the alarm cable, the alarm will remain raised until the alarm cable is connected.



Note When you provision an external alarm, the alarm object is ENV-IN-nn. The variable nn refers to the external alarm's number, regardless of the name you assign.


21.7.2  External Controls

You can provision each alarm output separately. Provisionable characteristics of alarm outputs include:

Control type.

Trigger type (alarm or virtual wire).

Description for CTC display.

Closure setting (manually or by trigger). If you provision the output closure to be triggered, the following characteristics can be used as triggers:

Local NE alarm severity—A chosen alarm severity (for example, major) and any higher-severity alarm (in this case, critical) causes output closure.

Remote NE alarm severity—Similar to local NE alarm severity trigger setting, but applies to remote alarms.

Virtual wire entities—You can provision an alarm that is input to a virtual wire to trigger an external control output.

21.7.3  Virtual Wires

Provisioning the AIC and AIC-I card provides a "virtual wires" option used to route external alarms and controls from different nodes to one or more alarm collection centers. In Figure 21-4, smoke detectors at Nodes 1, 2, 3, and 4 are assigned to Virtual Wire #1, and Virtual Wire #1 is provisioned as the trigger for an external bell at Node 1.

Figure 21-4 External Alarms and Controls Using a Virtual Wire

When using AIC virtual wires, you can:

Assign different external devices to the same virtual wire.

Assign virtual wires as the trigger type for different external controls.


hometocprevnextglossaryfeedbacksearchhelp